HomeMy WebLinkAbout12/09/2025 07.J. Resolution approving Change Order#1 for new fire panel at Yakima Air Terminal for the Terminal Modernization Baggage Claim Project � F s BUSINESS OF THE CITY COUNCIL YAKIMA, WASHINGTON AGENDA STATEMENT Item No. 7.J. For Meeting of: December 9, 2025 ITEM TITLE: Resolution approving Change Order#1 for new fire panel at Yakima Air Terminal for the Terminal Modernization Baggage Claim Project (No General Fund Impact) SUBMITTED BY: Gary Bellew, Assistant City Manager SUMMARY EXPLANATION: In early October, rain infiltration caused the existing airport terminal fire panel to short. The system is old and replacement parts to repair the system are unavailable. The airport has been on fire watch (regular patrols of the terminal building during occupancy) since the panel went down. This change order will replace the fire panel system within the Yakima Air Terminal that will make the terminal compliant with the fire codes, modernize the system and lower the cost of maintenance by utilizing a non-proprietary system allowing contracting with a local vendor. The existing system was proprietary and required call outs from Spokane. The replacement is added to the Baggage Claim project and costs are allocated 90°/o to the FAA and 10°/a to the YKM Airport. ITEM BUDGETED: Yes STRATEGIC PRIORITY 24-25: A Thriving Yakima RECOMMENDATION: Adopt Resolution. ATTACHMENTS: 2025_12_09_Change Order 01 Baggage Claim Project_Resolution.docx Change Order 01 Fire Alarm System Replacement 76 RESOLUTION NO. R-2025- A RESOLUTION authorizing the City Manager to execute Change Order No. 01 for the Fire Alarm System Replacement at the Yakima Air Terminal — McAllister Field. WHEREAS, the City owns and operates the Yakima Air Terminal-McAllister Field in accordance with applicable Federal, State, and Local regulations; and WHEREAS, the City has entered into a contract with Cliff Thorn Construction for the YKM Terminal Modernization project (Contract No. 1009251, dated April 17, 2025); a WHEREAS, the existing proprietary fire alarm system at the terminal has failed, is non- operational, and cannot be repaired due to obsolescence, requiring the City to conduct a fire watch; and WHEREAS, Change Order No. 01 provides for the replacement of the fire alarm system with a new Silent Knight Voice Evacuation system, including all associated labor, materials, and programming, at a cost of$170,044.94, with no change in contract time; and WHEREAS, in accordance with City policy, change orders in excess of$100,000 require City Council approval; and WHEREAS, the City Council finds it to be in the best interest of the City and the public to proceed with the execution of Change Order No. 01 to ensure the safety and functionality of the terminal facility; BE IT RESOLVED BY THE CITY COUNCIL OF THE CITY OF YAKIMA: The City Manager is hereby authorized to execute Change Order No. 01 to the contract with Cliff Thorn Construction for the YKM Terminal Modernization project, in the amount of $170,044.94, for the replacement of the fire alarm system at the Yakima Air Terminal — McAllister Field. ADOPTED BY THE CITY COUNCIL this 9th day of December, 2025. Patricia Byers, Mayor ATTEST: Rosalinda Ibarra, City Clerk 1 77 : k City of Yakima Change Order NumberChange Order 01 Project Name: YKM Terminal Modernization W02 WP1 Baggage Claim Change Order Date 11/11/2025 Project Number: AIP Supp 3-53-0089-058-2024 Contract Number 1009251 Contract Date 04/17/2025 Contractor: Cliff Thorn Construction 1552 Georgia Ave Address: Richland,WA 99352 City,State,Zip: You are directed to make the following changes in this Contract: Replacing the existing proprietary fire alarm system with a new Silent Knight Voice Evacuation fire alarm system. Currently the panel is non-operational and the City of Yakima Air Terminal is conducting fire watch. There is no option to repair the existing fire alarm panel as it is well past its useful life and not repairable. Please see the attached FAA Change order form for additional details, and required signature fields. Not valid until signed by both the Approving Authority and Contractor. Signature of the Contractor indicated agreement herewith,including any adjustment on the Contract Sum or Contract Time. The original Contract Sum was $ 2,471,229.00 Net change by previous Change Orders $ 0.00 The Contract Sum prior to this Change Order $ 2,471,229.00 The Contract Sum will be: 9 Increased 0 Decreased 0 Unchanged by this Change Order $ 2,641,273.94 The New Contract Sum including this Change Order will be $ 2,641,273.94 The Contract Time will be: 0 Increased 0 Decreased 0 Unchanged by 0 averleing-day3 calendar days The New Contract Time will be 210 -days calendar days Contractor Approval Recommended Approval Recommended Project Engineer City of Yakima-Division Director BY Ly Title Project Manager BY Q" By Date 12/02/2025 Date City of Yakima-Division Manager Approved Date 11/11/2025 Victoria Baker,City Manager BY By Date Date Based on Original to: 0 Contractor Copies to: 0 Region 0 Construction Administrator DOT Form usi ff 0 OSC Accounting 0 City Engineering Revised78 Page 1 of 2 pages CONTRACT CHANGE ORDER NO. 01 or SUPPLEMENTAL AGREEMENT NO. AIRPORT Yakima Air Terminal— DATE November 11,2025 McAllister Field (YKM) LOCATION Yakima,WA AIP PROJECT NO. 3-53-0089-058-2024 CONTRACTOR Cliff Thorn Construction You are requested to perform the following described work upon receipt of an approved copy of this document or as directed by the engineer: Item Unit No. Description Unit Price Quantity Amount LS CO1 FIRE ALARM PANEL 170,044. 1 170,044.94 REPLACEMENT 94 This Change Order Eligible Total $170,044.94 This Change Order Ineligible Total $0.00 This Change Order Total $170,044.94 Previous Contract Total $2,471,229.00 Revised Contract Total $2,641,273.94 The time provided for completion in the contract is increased by 0 calendar days. This document shall become an amendment to the contract and all provisions of the contract will apply. Changes are shown on Drawing(s)No.N/A. Recommended by: Leslee Randolph 11/11/2025 MWA ARCHITECTS Date (Engineer) Approved by: City of Yakima(Owner) Date Accepted by: (Contractor) Date Concurred by: N/A N/A State Aeronautics (if applicable) Date 79 Page 2 of 2 pages AIP PROJECT NO. 3-53-0089-058-2024 CHANGE ORDER NO. 01 (Supplemental Agreement) AIRPORT Yakima Air Terminal—McAllister LOCATION City of Yakima,WA Field (YKM) JUSTIFICATION FOR CHANGE 1. Brief description of the proposed contract change(s) and location(s). Replacing the existing proprietary fire alarm system with a new Silent Knight Voice Evacuation fire alarm system. 2. Reason(s) for the change(s) (Continue on reverse if necessary) Currently the panel failed not due to construction activities and is non-operational and the City of Yakima Air Terminal is conducting fire watch. This project is replacing strobes and alarms as part of the project and has no mechanism to modify the fire alarm system due to catastrophic systems failure. There is no option to repair the existing fire alarm panel as it is well past its useful life and not repairable. 3. Justifications for unit prices or total cost. An independent cost analysis has been prepared as follows: Labor Journeyman 158.00 hours rate $131.13 = $20,718.54 Journeyman 198.72 hours rate $131.13 = $26,058.15 Journeyman 1.87 hours rate $131.13 = $245.21 Journeyman 149.72 hours rate $131.13 = $19,632,78 Journeyman 1.47 hours rate $131.13 = $192.76 Journeyman 6.73 hours rate $131.13 = $882.50 Journeyman 82.80 hours rate $131.13 = $10,857.56 Total Labor: $78,587.50 Material costs: Conduit, Boxes, Supports $2,940.03 FA Cables, Terminations $4,319.60 Red FA Panel Receptors $27.25 E3 Quoted FA System Devices $21,780.29 Breaker and Breaker Lock$195.50 Cable Straps/Supports $37.89 E3 Sub Program/Test/Training $15,991.90 Total Material Cost: $29,300.56 Prime Contractor Markup 15% Total cost of independent estimate: $170,044.94 Detailed costs provided by the contractor were as follows: Journeyman 158.00 hours rate $131.13 = $20,718.54 80 Journeyman 198.72 hours rate $131.13 = $26,058.15 Journeyman 1.87 hours rate $131.13 = $245.21 Journeyman 149.72 hours rate $131.13 = $19,632,78 Journeyman 1.47 hours rate $131.13 = $192.76 Journeyman 6.73 hours rate $131.13 = $882.50 Journeyman 82.80 hours rate $131.13 = $10,857.56 Total Labor: $78,587.50 Material costs: Conduit, Boxes, Supports $2,940.03 FA Cables, Terminations $4,319.60 Red FA Panel Receptors $27.25 E3 Quoted FA System Devices $21,780.29 Breaker and Breaker Lock$195.50 Cable Straps/Supports $37.89 E3 Sub Program/Test/Training $15,991.90 Total Material Cost: $29,300.56 Silent Knight Voice Evacuation Fire Alarm System $142,461.95 B&O Tax $800.91 General Liability Insurance $1,275.34 GC O&P $25,506.74 4. The sponsor's share of this cost is available from: County funding made available to the City/Airport for matching funds. 5. If this is a supplemental agreement involving more than$2,000, is the cost estimate based on the latest wage rate decision? Yes ❑ No ❑ Not Applicable ❑. 6. Has consent of surety been obtained? Yes ❑ Not Necessary ❑. 7. Will this change affect the insurance coverage? Yes ❑ No ❑. 8. If yes, will the policies be extended? Yes ❑ No ❑ Not Applicable ❑. Comment 81 Change Order Cliff Thorn Construction Order#: 3 CTC 1552 SE Georgia Ave Richland WA 99352 Order Date: 11/11/2025 (509)416-2007 CUFF THORN CONSTRUCTION,LLC License: CLIFFTC891P8 To: City of Yakima Project: 25034 129 North Second Street Yakima Air Terminal Baggage Claim Yakima WA 98901 3110 W Washington Ave Yakima WA 98903 The contractor agrees to perform and the owner agrees to Plans Attached pay for the following changes to this contract. Ordered By: 159 Jess Metzger Customer Order: Specifications Attached ❑ Description of Work Amount Silent Knight Voice Evacuation Fire Alarm System 142,461.95 Monitoring Contract with E3 Solutions$40/mo. NOT INCLUDED-TSA Panic Security Panel in COR#4. B&O Tax 800.91 General Liability Insurance 1,275.34 GC O&P 25,506.74 Notes Negative changes will lower the overall contract price requiring no additional payment by owner. Requested Amount of Change 170,044.94 The original Contract Sum was 2,471,229.00 Net change by previous Change Orders 0.00 The Contract Sum prior to this Change Order 2,471,229.00 The Contract Sum will be changed by this Change Order 170,044.94 The new Contract Sum including this Change Order will be 2,641,273.94 The Contract Time will be changed by 0 Days Owner: Date: Contractor: Date: 11/11/2025 82 YKM WP-01 Baggage Claim 10092501 2300 W.Washington Ave,Yakima,Washington,98903 KINTER ELECTRIC Kinter Electric //�} �i 2761 E Edison Rd.,Sunnyside,Washington,98944 Phone(425)830-2270 Change Order Request No. 3 FIRE ALARM REPLACEMENT- Return By 11/14/2025 TO REPLY TO Jess Metzger(CTC) Josh Radosevich Internal jess@ctcbuilds.com josh@kinterelectric.com (509)792-2386 GENERAL INFO Date Days Valid Work Type GC COR No. 11/06/2025 7 Directed Change SCOPE OF WORK RRE:YKM Air terminal Baggage Area Project—CO#1 Fire Alarm Phase 1 **Monitoring Contract with E3 Solutions$40.00 per month.YKM contact Rick Woods for details. Please consider our proposal for this project.We propose replacing the existing proprietary fire alarm system with a new Silent Knight Voice Evacuation fire alarm system.This product is available to all qualified fire alarm contractors and can be serviced by numerous contractors in the Yakima area. Please note:This proposal assumes that all conduit and cabling be provided by the electrical contractor. It was noted that the existing fire alarm is fully in conduit and to maintain this standard this system will be as well. (Temporarily cabling by electrician will be open until remodeling takes place in these areas) Based on current WAC,the cable must also be installed by an 01 Journeyman Electrician. We will provide a fire alarm system that is sized to be expandable to what is required for all phases of the construction for this facility.This initial quote includes all head end equipment and devices for the current public areas as approved by the Fire Marshal. In addition to monitoring the sprinkler system we will provide and install required equipment for the main elevator recall functionality(will require owner contacts with their elevator contractor to coordinate this work).We will also monitor the three new duct smoke detectors that will be included in new RTU's. We will provide and install the following based on our initial design. • 1—Silent Knight 6820EV5 Voice Evac Fire Alarm Panel • 1—Silent Knight EVS-125W Voice Amplifier • 1—Silent Knight EVS-LOC Remote Command Center • 1—Silent Knight SK-5496 Auxiliary Power Supply • 1—Telguard TG-7FE-A Dual Path Communicator • 5—Silent Knight SK-PHOTO-W Photelectric Smoke Detectors • 1—Silent Knight SK-HEAT-W Addressable Heat Detectors • 3—Silent Knight SK-MONITOR Addressable Input Modules(for Duct Smokes) • 2—Silent Knight SK-MONITOR2 Addressable Input Modules(for Sprinkler System) YKM WP-01 Baggage Claim 10092501 Page 1 of 4 Change Order Request No. 83 • 3—Silent Knight SK-RELAY Addressable Relays(Elevator Recall) •41—System Sensor Speaker Strobes All existing non-operable Simplex Devices must be removed and boxes blanked off per code. Proposal does not include any of the new work required in the Baggage Claim contract documents. 2nd Floor non-operable Simplex Devices will be removed, boxes blanked off,and raceways repaired and preserved for future. Exclusions and Notes: • Duct Smoke Detectors or installation of Duct Smoke Detectors. • Fire/Smoke Dampers or control of Fire/Smoke Dampers •Any fire stopping material or installation of fire stopping material. •Any Devices not included in this proposal. We shall provide a one-year warranty covering all system components,materials,and labor and workmanship from the date of acceptance or beneficial use-whichever occurs first,excepting any parts,components or services provided by other suppliers/contractors which have been directly provided to the customer. Warranty does not cover repair of damage(s)caused by accident,disaster and other force majeure events,including but not limited to fire,flood,water, wind, lightning,neglect,acts of terrorism, misuse and/or unauthorized alterations,or attempted repairs made by non-factory certified persons. Warranty service calls will be made during normal business hours.Warranty calls made during non-business hours shall be billed at the prevailing after-hours service rate SCHEDULE IMPACT No.of Days 30 Comments Duration to complete added scope. DETAILED VIEW YKM WP-01 Baggage Claim 10092501 Page 2 of 4 Change Order Request No. 84 No. LABOR Hours Workers Rate Extended 1. Journeyman 158.00 hrs 2 $131.13 $20,718.54 Notes:100 BRANCH 2. Journeyman 198.72 hrs 2 $131.13 $26,058.15 Notes:300 WIRE/TERMINATIONS 3. Journeyman 1.87 hrs 2 $131.13 $245.21 Notes:500 DEVICE TRIM 4. Journeyman 149.72 hrs 2 $131.13 $19,632.78 Notes:600 L-V SYSTEMS 5. Journeyman 1.47 hrs 2 $131.13 $192.76 Notes:700 GEAR/EQUIPMENT 6. Journeyman 6.73 hrs 2 $131.13 $882.50 Notes:800 STRAPS/SUUPORTS 7. Journeyman 82.80 hrs 2 $131.13 $10,857.56 Notes:910 DEMO SIMPLEX FA SYSTEM DEVICES Total Labor Expense $78,587.50 No. MATERIAL Qty UM Rate Extended 1. Conduit, Boxes,Supports 1 Each $2,940.03 $2,940.03 Notes:Conduit,Boxes,Supports 2. FA Cables,Terminations 1 Each $4,319.60 $4,319.60 Notes:FA Cables,Terminations 3. Red FA Panel Recep 1 Each $27.25 $27.25 Notes:Red FA Panel Recep 4. E3 Quoted FA System Devices 1 Each $21,780.29 $21,780.29 Notes:E3 Quoted FA System Devices 5. Breaker and Breaker Lock 1 Each $195.50 $195.50 Notes:Breaker and Breaker Lock 6. Cable Straps/Supports 1 Each $37.89 $37.89 Notes:Cable Straps/Supports Total Material Expense $29,300.56 YKM WP-01 Baggage Claim 10092501 Page 3 of 4 Change Order Request No. 85 No. SUBCONTRACTOR Qty UM Price Extended 1. E3 Sub Program/Test/Training 1 Each $15,991.90 $15,991.90 Total Subcontractor Expense $15,991.90 SUMMARY Category Extended Markup Total Labor $78,587.50 $11,788.13 $90,375.63 (15%) Material $29,300.56 $4,395.08 $33,695.64 (15%) Subcontractor $15,991.90 $2,398.78 $18,390.68 (15%) Total $142,461.95 Tax $0.00 GRAND TOTAL $142,461.95 RESERVATION OF RIGHTS This COR does not include any amount for impacts such as interference,disruptions, rescheduling,changes in the sequence of work,delays and/or associated acceleration. We expressly reserve the right to submit our request for any of these items. YKM WP-01 Baggage Claim 10092501 Page 4 of 4 Change Order Request No. 86 e e3 Solutions, Inc. P.O. Box 72 •Yakima, WA 98907-0072 °LA Phone (509)452-0240♦ Fax (509)452-3001 •Toll Free (866)452-0240 °°,s 4 �� On the Web at http://www.ecubedsolutions.com City of Yakima WP-01 Baggage Claim and Terminal Eastside Passenger Areas 2300 W Washington Avenue Yakima, WA 98903 Project No: 202418.21 Fire Alarm Submittal 87 All information contained herein, including but not limited to,oral statements,computer files,drawings, personnel files, professional references,and other material or data supplied to the client is confidential and privileged. 6820Evs Intelligent Fire Alarm Control Panel with Emergency Voice System The 6820EVS panels and accessories provide features to meet the requirements for Mass . Notification Systems as described in UL 2572 ..... a. e.« . 2nd Edition and UL 86410th Edition. The 6820EVS is an intelligent addressable Fire Alarm Control Panel combined with an Emergency Voice System(EVS)and are direct replacements for the 5820XL-EVS FACP. When the EVS features are enabled,they are integrated with the fire alarm and voice evacuation functions of the control panel. E E E ME The emergencyvoice system operations include an onboard supervised microphone.All-call and non-active call buttons can quickly select all active or non-active output groups.The . . . --o j,: F;:, system also allows for emergency messages over fire. The 6820EVS FACP has one built-in signaling line circuit(SLC),which can support 159 SK detectors and 159 SK modules,or 127 SD protocol devices.Additional SLC loops can be added for a maximum of 1110(SK)or 635(SD)points per panel. The built-in digital alarm communicator/transmitter(DACT)is dual technology,IP and POTS.The POTS transmits system status(alarms,troubles,AC loss,etc.)to a Central Station via the public switched telephone network.The IP communicator's internet monitoring capability sends alarm signals over the Internet saving the monthly cost of two dedicated business telephone lines.Although not required,the secondary telephone line may be retained providing backup communication over the public switched telephone line.Optional cellular reporting is available. The 6820EVS has six onboard Flexput®circuits that can be configured as notification outputs or auxiliary power.The 6820EVS also has a form-C trouble relay,and two programmable form-C relays,along with powerful features such as drift compensation,pre- trouble maintenance alert,a built-in sensor test to comply with NFPA 72 calibration testing requirements,and a calibration trouble alert. A common communications and annunciation link allows up to 17 panels to be connected via copper or fiber optic cable.A designated panel is configured as the communicator for all panels in the link for convenient single-point communications. FEATURES AND BENEFITS • Single enclosure for both fire and • Selectable strobe synchronization for • Two programmable relays and one fixed emergency voice components Amseco®,System Sensor®,Wheelock®,and trouble relay • Ability to select EVS messages as priority Gentex°devices • Compatible with SWIFT°wireless devices over fire • BuiLt-in DACT with IP and optional cellular • Convenient field-upgradeablefirmware • 15 Recordable one-minute messages that reporting • Network support for up to 17 sites can be mapped to eight EVS buttons • Built-in USB interface for quick and easy • Network card allows copper network • Capable of producing 520 Hz tones to meet programming connection with a multi-mode or single- NFPA 72 requirements • JumpStart°auto programming reduces mode fiber connection • Support for up to 4 LOC consoles and 8 installation time • Real-time clock/calendar with automatic addressable amplifiers • 999 software zones&999 output groups daylight savings control • Expandable SLC loops to 1110(SK)or 635 for flexible design options • History file with 1,000 event capacity (SD)point capacity • 23 preset notification cadence patterns • Six Flexput circuits for NAC outputs or (including ANSI°3.41) auxiliary power • Allows up to 24 SBUS devices• Four programmable function keys Honeywell rn SILENT Ilia KNIGHT 88 Pg.1 USER INTERFACE SK COMPATIBLE ADDRESSABLE DEVICES LED INDICATORS Note:SKand SD devices cannot be mixed in the same fire alarm system. • General Alarm(Red) • Supervisory(Yellow) SK-ACCLIMATE: Multi criteria photoelectric smoke detector with thermal 135 F fixed temperature • System Trouble(Yellow) • System Silenced(Yellow SK-BEAM:Reflected beam smoke detector without test feature • System Power(Green) SK-BEAM-T: Reflected beam smoke detector with test feature KEYPAD OSI-RI-SK:Reflected beam smoke detector,SK protocol • 12-key numeric pad SK-CONTROL:Supervised control module • Acknowledge SK-CONTROL-6:Six circuit supervised control module • Alarm Silence SK-DUCT: Photoelectric duct smoke detector with extended air • System Reset speed range • Drill SK-FIRE-CO:Four criteria fire and carbon monoxide detector • F1-F4 Programmable Function Keys SK-FIRE-CO-W:Four criteria fire and carbon monoxide detector, white PROGRAMMING SK-H EAT:Fixed thermal detector(135°F) The 6820EV5 system offers several options to simplify and expedite SK-HEAT-W:Fixed thermal detector(135°F),white programming.JumpStart°auto programming minimizes SK HEAT ROR: Fixed rate of rise detector programming required to start a new system.The built-in keypad,or the remote annunciators give on-site access to current system SK-HEAT-HT: Fixed high temperature heat detector(190°F) programming.System programming can also be accomplished SK-HEAT-HT-W:Fixed high temperature heat detector(190°F), using the Windows°-based Honeywell Fire Software Suite(HFSS). white ORDERING INFORMATION SK-HEAT-ROR-W:Fixed rate of rise detector,white 6820EVS:Addressable fire alarm control panel with emergency SK ISO:Fault isolator module voice system,red SK-MINIMON:Mini monitor module COMPATIBLE EVS EQUIPMENT SK-MONITOR:Monitor module EVS-50W:50 Watt amplifier SK-MONITOR-2:Dual input monitor module EVS-125W:125 Watt amplifier SK-MON-10:10-input monitor module EVS-100W:50/100 Watt amplifier SK-PHOTO: Photoelectric smoke detector EVS-100WBU:External backup amplifier SK-PHOTO-W:Photoelectric smoke detector,white EVS-INT50W:50/Watt internal amplifier SK-PHOTO-R: Photoelectric detector with remote test capability EVS-CE4:Provides 4 additional audio circuits SK-PHOTO-R-W:Photoelectric detector with remote test capability, white EVS-RVM:Remote voice module SK-PHOTO-T:Photoelectric smoke detector with fixed heat(135°F) EVS-SW24:24 switch expander SK-PHOTO-T-W:Photoelectric smoke detector with fixed thermal EVS-VCM:Network voice control module heat(135°F),white EVS-LOC: Local operator console SK-PTIR-W:Multi criteria photoelectric smoke detectorwith thermal COMPATIBLE SBUS DEVICES 135°F fixed temperature,white 6860:4x40 LCD remote fire annunciator with four programmable SK-PULL-SA AddressabLe single action pull station buttons,red SK-PULL-DA:Addressable dual action pull station 5860:4x20 LCD remote fire annunciator,gray SK-RELAY:AddressabLe relay module 5860R:4x20 LCD remote fire annunciator,red SK-RELAY-6:Addressable Six relay control module 6855:4x20 LCD remote fire annunciator,red SK-RELAYMON-2:AddressabLe DuaL relay/monitor module 5865-3: LED annunciators-display up to 30 LEDs(15 red/15 SK-ZONE:Addressable zone interface module yellow) SK-ZONE-6:Six zone interface module 5865-4: LED annunciators-display up to 30 LEDs(15 red/15 yellow).Key switches for silence and reset,and a system trouble LED 5880:LED I/O module with 40 programmable LED outputs and eight supervised dry contact inputs 5883: Relay interface. Provides 10 Form C relays 5824:Serial/Parallel printer interface module for printer connection Page 2 of 4—351606:E•3/7/2022 89 Pg.2 SK BASES SYSTEM EXPANDERS B210LP:6"mounting base 6815:SLC Expander for IDP or SK devices B501:4"Flangeless mounting base 5815XL:SLC expander for SD devices B200S:Intelligent sounder base RPS-1000:6A power supply with 6 Flexput circuits&2 Form C B200S-LF: Low-frequency intelligent sounder base relays B224RB:Relay base 5496:6 amp NAC power expander with 4 power-Limited output ckts B224B1: Isolator base OPTIONAL COMMUNICATORS SD COMPATIBLE ADDRESSABLE DEVICES CELL-CAB-SK:Cellular communicator,metal encLosure w/Lock& key Note:SK and SD devices cannot be mixed in the same fire alarm CELL-MOD:Cellular communicator,plastic encLosure system. IPGSM-4G:Dual path fire aLarm communicator,cellular and/or IP SD505-6AB:Addressable 6"base (primary or backup,selectable) SD505-61B:Addressable 6"short circuit isolator base SK-IP-2:Remote reporting via the Internet.Requires a VisorALARM° SD505-6RB:AddressabLe 6"relay base receiver at the central station SD505-6SB:AddressabLe 6"sounder base MISCELLANEOUS ACCESSORIES SD500-AIM:AddressabLe input module(switch input) SK-NIC:Network Interface Card.Provides a common SD500-ANM:Addressable notification moduLe communications link for the IFP-300 SD500-ARM:Addressable reLay moduLe SK-N IC-KIT: Installation Accessory Kit SD505-DTS-K:Remote test switch/LED indicator for the SK-FML: Fiber Optic Multi Mode,transmitter and receiver SD505-DUCTR SK-FSL:Fiber-Optic SingLe Mode SD505-DUCT:AddressabLe Duct Smoke Detector RBB: Remote battery box accessory cabinet SD505-DUCTR:AddressabLe Duct Detector housing with relay base SK-SCK:Seismic compliance kit used to fasten batteries to the fire SD505-HEAT:Absolute temperature heat detector.Trip point range panel from 135°F-150°F(0°C-37°C) SOFTWARE SOLUTIONS SD500-LIM:Addressable Line isolator moduLe SKST:Silent Knight Selection Tool provides the installer or design SD500-MIM:Addressable Mini input monitor moduLe(switch input) architect with a Windows°-based software system configuration tool to create a detailed bill of material(BOM)and battery SD505-PHOTO:Photoelectric smoke detector calculations SD500-PS/-PSDA:AddressabLe SingLe or dual action pull station HFSS:Honeywell Fire Software Suite provides remote and Local SD500-SDM:AddressabLe smoke detector moduLe panel programming,detector status,event history and additional SWIFT WIRELESS DEVICES data.Databases can be uploaded/downloaded via the panel's USB port using a flash drive.Requires a PC running Microsoft° Note:SWIFT is only compatibLe with System Sensor(SK)devices. It Windows®. is not compatibLe with Hochiki(SD)devices. WSK-WGI:WireLess gateway WSK-PHOTO:Wireless photoeLectric smoke detector with B501W base WSK-PHOTO-T:WireLess photoeLectric smoke detector with fixed thermal detection(135°F)and B501W base W-SYNC:WireLess sync module WSK-HEAT::Wireless,fixed heat detector(135°F)with B501W base WSK-HEAT-ROR:Wireless rate-of-rise heat detector and B501W base WSK-MONITOR:Wireless monitor module WSK-RELAY:Wireless relay moduLe WSK-PULL-DA:WireLess pull station WAV-RL,WAV-WL,WAV-CRL,WAV-CWL:Wireless AV bases W-USB:Wireless USB radio/antenna dongLe that plugs into the USB port of a PC running SWIFT Tools SWIFT TooLs: Programming and diagnostic utility for the wireless gateway and devices.Available for download from www.farenhyt.com 351606:E•3/7/2022 — Page 3 of 4 90 Pg.3 6820EVS TECHNICAL SPECIFICATIONS SYSTEM CAPACITY TEMPERATURE AND HUMIDITY Intelligent Signaling Line Circuits:1 RANGES Flexput°, Honeywell®,JumpStart°, (expandable) This system meets NFPA requirements for Silent Knight®,SWIFT°,and System Addressable device capacity:1110(SK)or operation at 0—49°C(32—120°F)and at a Sensor°are registered trademarks 635(SD) relative humidity 930/0±20/0 RH(non- of Honeywell International Inc. Programmable software zones:999 condensing)at 32°C±2°C(90°F±3°F). Amseco®is a registered trademark However,the useful Life of the system's of Potter Electric Signal Company, Output circuits:6(expandable) standby batteries and the electronic LLC.Gentex°is a registered SBUS devices:24(16 annunciators,8 LED components may be adversely affected by modules) extreme temperature ranges and humidity. trademark of Gentex Corporation. Therefore,it is recommended that this Hochiki°is a registered trademark LOC units:4 system and its peripherals be installed in an of Hochiki Corporation.Wheelock° Addressable amplifiers(total watts):8 environment with a normal room is a trademark of Cooper (1000) temperature of 15—27°C/60—80°F. Technologies Company.ANSI®" is a ELECTRICAL STANDARDS AND CODES registered trademark of the AC Power:120VAC,60Hz,3.3A The 6820 complies with the following American National Standards Standby Current:190 mA standards and codes: Institute, Inc.VisorALARM°is a Alarm Current:250 mA NFPA 72 registered trademark of the Teldat NFPA 13 Corporation. Microsoft°and Flexput Circuits:Terminal block provides Windows® connections for(six Class B orthree Class A) NFPA 15 Windowsare registered NACs or auxiliary power.Power-Limited, N FPA 16 trademarks of Microsoft supervised circuitry.Maximum current per NFPA 70 Corporation. circuit:3 A.Cannot exceed 6A total for all UL 86410th Edition circuits.End-of-line resistor:4.7k ohm,1/2 This document is not intended to be watt for Class B NACs UL2572 2nd Edition used for installation purposes.We Communication Loop:Supervised and Central station;remote Signaling;Local try to keep our product information power-Limited,Class A or Class B,32VDC, Protective Signaling Systems;Auxiliary up-to-date and accurate.We cannot 150mA Protected Premises Unit;Water Deluge releasing service.Suitable for automatic, cover all specific applications or Two Programmable Relays and One Fixed manual,waterflow,sprinkler supervisory anticipate all requirements.All Trouble Relay:Contact rating:2.5 A 27.4 (DACT non-coded)signaling services specifications are subject to change VDC(resistive),Form C without notice. Battery:Cabinet holds maximum of two 18 AGENCY LISTINGS AND AH batteries APPROVALS Country of origin:USA Battery Charger Capacity:7-35 AH UL Listed: S2766 PHYSICAL CSFM:7165-0559:0500 Dimensions:21.6"W x 28.1"H x 5.1"D FDNY: COA#6249 (54.9cm W x 71.4cm H x 13.0cm D) FM:Approved Weight:50 lbs.(22.7 kg.) Seismic:(CA)VMA-45894-05C: Color:Red Honeywell Silent Knight 12 Clintonville Road Northford,CT 06472-1610 Honeywell 203.484.7161 351606 I E 104/22 SILENT' www.silentknight.com ©2022 Honeywell International Inc. ®KNIGHT 91 Pg.4 Intelligent 125 Watt Amplifier The EVS-125W is an amplifier compatible with the Silent Knight Emergency Voice IIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIIII System. The EVS-125W is used to amplify audio messages for distribution throughout entire facilities. Since the EVS-125W is designed as a self-contained distributed amplifier,it can be conveniently Located near the area of protection to reduce wiring demands.Each EVS-125W is capable of producing 125-watts of audio power.Up to four EVS-125W amplifiers can be used on the Emergency Voice System.The EVS-125W has its own power supplywith battery backup and includes four speaker circuits which can be expanded to eight speaker circuits when used with the optional EVS-CE4.The EVS-125W is fully supervised by the main paneL to identify any trouble conditions. INSTALLATION The EVS-125W can be surface-or flush-mounted. COMPATIBILITY The EVS-125W is compatible with the 6820EVSAddressable FACP with Emergency Voice »e System. FEATURES AND BENEFITS • Complies with UL 864 10th Edition and UL EVS-CE4 expander,fora system total of 32 • Provides six-wire connection to the EVS 2572 2nd Edition Standards audio circuits system: • Meets NFPA 72 standards • Uses an easy-to-install wire harness to -Two wires for voice bus connections • SBUS addressable;supports up to four connect the EVS-CE4 audio circuit -Four wires for SBUS connections EVS-125W amplifiers per system for a total expander • Can be surface-or flush-mounted of 500 watts • Mountable up to 6,000 feet away from the • Supervised wiring with four onboard audio EVS paneL circuits,expandable to eight with the • Includes power supply and backup battery Honeywell ® SILENT' KNIGHT 92 Pg.5 EVS-125W TECHNICAL SPECIFICATIONS PHYSICAL ORDERING INFORMATION Flush Mount Dimensions: EVS-125W:Intelligent 125W Amplifier,red Honeywell°and Silent Knight°are 14.05"W x 24.75"H x 3.04"D registered trademarks of Honeywell (36.08 W x 62.09 H x 8.07 D cm) ACCESSORIES International, Inc. Overall Dimensions: EVS-CE4:Audio Circuit Expander This document is not intended to be 16.0"W x 26.25"H x 4.01"D RBB:Remote Battery Box accessory used for installation purposes.We (40.06 W x 66.07 H x 10.05 D cm) cabinet.Use for backup batteries up to Color:Red 35AH and batteries too Large to fit into an try to keep our product information EVS-125W cabinet. up-to-date and accurate.We cannot ENVIRONMENTAL SK-SCK:Seismic Compliance Kit cover all specific applications or Operating Temperature:32°F to 120°F anticipate all requirements.All (0°C to 49°C) STANDARDS AND CODES specifications are subject to change Humidity:100/0to 93°/o relative humidity The EVS-125W Series complies with the without notice. (non-condensing) following standards and codes. • UL 864,10th Edition:Standard for Control Country of origin:USA ELECTRICAL Units for Fire ALarm Systems Primary AC:120 VAC @ 60Hz • UL 864,Local Protective Signaling Systems Standby Current:300mA • UL 2572,2nd Edition:Standard for Mass Alarm Current:2200mA Notification Systems Total Power:125W @ 25VRMS • UL 1711 • Circuit 1:Rated at 100W each • NFPA 13,NFPA 70,NFPA 72 • Circuit 2-4:Rated at 50W each AGENCY LISTINGS AND EVS-CE4 Circuits 5-8:Rated at 50W each APPROVALS Main EVS Panel SBUS: • UL Listed:S2766 Standby Current:10mA • CSFM Approved:7165-0559:0500 Alarm Current:10mA • FDNY:COA#2023-TMCOAP-001920- Battery Charging Capacity:7—35AH RENL Battery Size:18AH max.allowed in the cabinet.Use the RBB accessory cabinet for larger batteries up to 35AH per system. Voice Integration Wiring(Six Connectors): • Two voice bus • Four SBUS Honeywell Silent Knight 12 Clintonville Road Northford,CT 06472-1610 Honeywell 203.484.7161 350606 I D 109-23 ®SILENT' ell www.silentknight,com ©2023 Honeyw International Inc. KNIGHT 93 Pg.6 otiouse Local Operating Console The EVS-LOC is a combination of supervised remote microphone and annunciator which is compatible with the Silent Knight® EVS Series Emergency Voice System and meets UL _ • ••• requirements for a Local Operator Console. ... e The EVS-LOC provides an interface to the 6820EVS Emergency Voice System.It includes a it 11.1.1 supervised on-board microphone for live communications and its annunciator is capable of • . +� performing complete operation of the fire alarm system,including silencing and resetting. alE aiE The EVS-LOC aLso has four programmable function buttons which can be used to minimize time spent executing complex or routine tasks. The console's emergency communication system operations includes an onboard supervised microphone and buttons that allowyou to quickly select all active or all non- active output groups.The system also lets you select an EVS message as a priority over fire. - 71 COMPATIBILITY The EVS-LOC Local Operating Console is compatible with the following Silent Knight FACPs: • 6820EVS • 5820XL-EVS FEATURES AND BENEFITS • UL listed.Complies with UL 864,10th • Provides additional communications and • Accepts programmabLe trigger inputs from Edition;UL 2572,2nd Edition control options that are aLso available in the an external source,such as a Monaco® • Complies with NFPA 72 standard EVS primary paneL system,to either the EVS-RVM or 5880 • CSFM,FDNY,and FM approved • Extends system access to additional areas module • Up to 32 mappable speaker circuits can be • Large 4x40 LCD backlit screen with up to of a building or mass notification network connected to the EVS-LOC using a 160 available characters • Makes access to the communication combination of EVS-50W,EVS-100W,or • Includes 4 programmabLe buttons to system easier when immediate and timely EVS-125W amplifiers minimize time spent executing complex or communications are essential routine tasks • Up to four EVS-LOCs can be added to a compatible emergency voice system for a Honeywell total of five command units laSILENT KNIGHT 94 Pg.7 EVS-LOC TECHNICAL SPECIFICATIONS PHYSICAL STANDARDS AND Honeywell°and Silent Knight°are Dimensions: CODES registered trademarks of Honeywell 26.5"H x 20"W x 5.05" D International, Inc. (67.3 cm x 50.75 cm x 12.8 cm) The EVS-LOC complies with the following standards/codes: Mounting:Surface or Flush mount Monaco®is a registered trademark • UL 864,10th Edition:Standard for Control ENVIRONMENTAL of Monaco Enterprises, Inc. Units for Fire ALarm Systems Operating Temperature:32°F to 120°F • UL 2572,2nd Edition:Standard for Mass This document is not intended to be (0°C to 49°C) Notification Systems used for installation purposes.We Humidity:0%to 93%relative humidity • NFPA 72,National Fire Alarm and Signaling try to keep our product information (noncondensing) Code up-to-date and accurate.We cannot ELECTRICAL AGENCY LISTINGS AND cover all specific applications or Operating Voltage:24VDC APPROVALS anticipate all requirements.All specifications are subjectto change Standby Current:105 mA • UL Listed:S2766 without notice. Alarm Current:175 mA • FDNY:COA#6017,6122,6198,6296A, �+ 6299,6302A,6304 Country of origin:U.S.A. ORDERING • CSFMApproved INFORMATION • FM Approved EVS-LOC:Local Operator Console,Red ACCESSORIES EVS-CE4:Four-speaker Circuit Expander. Adds four audio circuits to EVS-50W,EVS- 100W,or EVS-125W amplifiers(see datasheets 350605,350961,and 350606) EVS-RVM:Remote Voice Module EVS-SW24:24 Switch Expander 6860:Remote Annunciator(see datasheet 351612) VIP-TR:Panel Trim Ring for flush mounting 5880:LED/10 Driver Module(see datasheet 350233) Honeywell Silent Knight 12 Clintonville Road Northford,CT 06472-1610 Honeywell 203.484.7161 351631 I B 102/22 ®SILENT` www.silentknight.com ©2022 Honeywell International Inc. KNIGHT 95 Pg.8 Honeywell Farenhyfm Series THE POWER OF CONNECTED 5496 Intelligent Power Module The 5496 intelligent power module is the most cost-effective power supply available today.It delivers 6 amps of notification appLiance circuit power and built-in synchronization for appliances from System Sensor°,Gentex°, AMSECO,and WheeLock®.The 5496's advanced microprocessor design is years ahead of the competition.Its switch mode power supply design is up to 50%more efficient than competitive linear mode power supplies. ) The 5496 is a 6 amp notification power expander that provides its own AC power connection,battery charging circuit,and backup battery for use with the Honeywell Farenhyt series fire alarm control panels(FACPs).The 5496 is the cost-effective solution for powering notification appliances required by the Americans with Disabilities Act(ADA).The 5496 has built-in ANSI cadence pattern.The output circuits can be programmed as notification appLiance circuits,or as auxiliary power(configurable for constant, resettable,or door holder power). 5496 COMPATIBILITY The 5496 is compatible with the following FACPs: • IFP-2100ECS/IFP-2100ECSB • IFP-2100/IFP-2100B/RFP-2100/RFP-2100B • IFP-2000/RPS-2000/IFP-2000ECS • IFP-300/IFP-300B/IFP-300ECS/IFP-300ECSB • IFP-1000/IFP-1000ECS • IFP-100/IFP-100ECS • IFP-75 • IFP-50 FEATURES & BENEFITS • UL Listed for 6 amps • Built-in • NACs are • Communicates to the • Lightweight design of notification power synchronization for programmable as FACP via 4-wire SBUS adds to ease of • Power su l s appliances from notification appliance (wire runs up to 6000 installation and pp y Gentex,AMSECO, circuits,or as auxiliary ft) reduces shipping advanced switch mode design reduces System Sensor,and power to be used as • AC loss delay option costs damaging heat and Wheelock constant,resettable, shuts off power to • ANSI Cadence pattern manages power up to • Four power-limited or door holder power non-essential high output capability 50%more efficiently notification outputs;2 • 3 amps per output current accessories built-in than other systems Class A or 4 Class B,or circuit like magnetic door • UL 864&1481 listed 1 Class A and 2 Class holders • 24 VDC filtered output B • Ground fault detector • OSHPD(CA) voltage •• CSFM approved MEA approved OSP-0065-10(see accessories) 96 Pg.9 5496 Technical Specifications Fora complete listing of all 4 Outputs Programmable compliance approvals and as Notification Appliance Circuits, certifications,please visit www.farenhyt.com. or as Auxiliary Power Microsoft,Windows,and the Windows Logo are Output 1 / SBUS Communication registered trademarks To a Compatible ortrademarksof Farenhyt Series FRCP Microsoft Corporation. Output 2 . Gentex°is a Registered Trademark of Gentex Output 3 . Corporation.Wheelock°is a Registered Trademark of Wheelock,Inc. Output 4 , SWIFT®,Honeywell®, and System Sensor®are registered trademarks AuxiliaryPower Can Be of and Farenhyt'""is k a Programmed To Be Constant, trademark of Honeywell Resettable, or Door Holder Power International,Inc. This document is not intended to be used for PHYSICAL ORDERING INFORMATION installation purposes.We Overall Dimensions:16"H x 12.25"Wx 3"D(40.6 x 5496:Intelligent Power Module try to keep our product 30.9 x 7.6 cm) information up-to Shipping Weight:8.71bs ACCESSORIES date and accurate.We RBB: Remote Battery Box Accessory Cabinet.16" cannot cover all spec pic applications or anticipate ENVIRONMENTAL W x 10"H x 6"D(406 mm W x 254 mm H x 152 mm all requirements.All Operating Temperature:32°F to 120°F (0°C to D) specifications are subject 49°C) SK-SCK: Seismic Compliance Kit to change without notice. Humidity:10 to 93°/o relative humidity(non- For Technical condensing) AGENCY LISTINGS AND APPROVALS Support,Please call • CSFM approved 800 446 6444. ELECTRICAL: AC Input:120VAC at 2.7A • N FPA 72 Output:24VDC at 6A • Standby&Alarm Current:10mA UL Listed Notification/Aux.Power Circuits:4 • FM approved Output Configuration: 2 Class A(Style Z) • City of NY:429-90-E Vol XIV 4 Class B(Style Y) 1 Class A&2 Class B Amps Per Output Circuit:3.0(6.0 amps total) Notification Circuit Output:20.4—27.3VDC @ 3.OA each End-of-Line Resistance:4.7k W EOL resistor required on each Class B circuit Battery Charging Capacity:7.0—35.0AH For more information Learn more about Honeywell's Farenhyt Series and other products available by visiting www.farenhyt.com Honeywell Security&Fire 12 Clintonville Road Northford,CT 06472 Doc 350302 Rev GI lvn Honeywell 800-328-0103 ©2017 Honeywell International Inc. 97 Pg.10 AP DUAL PATH INTERNET ' ' imp ND 5G LTE - M FIRE COMMUNICATOR l�1 COMMERCIAL FIRE Part of the full line of Telguard universal fire communicators, the TG-7FE offers two pathways to reliably transmit signals: a wired LAN connection DUAL PATH to the Internet and 5G LTE-M cellular. It operates on panel power or via (or plug-in transformer. vim/vim/ + PRODUCT FEATURES INTERNET 5G LTE-M IF Dual communication paths - If the Internet connection is interrupted or the LAN goes down, always-on 5G cellular will immediately step in. Powers directly from the fire panel's 12V/24V auxiliary power supply or via plug-in transformer (included). Uses LTE-M bands for 4G and 5G network compatibility, better in-building penetration, and longest product life. Interfaces with panel over a single DACT connection for universal compatibility (use TG-PEM accessory when panel has no DACT). Telguard communicators are compatible with more alarm formats than any other brand. The signal will reliably get to the central station. The world is changing. Copper POTS lines are disappearing, and calls are delivered over the Internet. This is a perfect example of where the TG-7FE steps in. Eliminate all Telco lines and run an Ethernet cable from the TG-7FE to the premises LAN for alarm signal delivery. And, to be sure signals get through to the central station you choose, the TG-7FE instantly falls over to reliable cellular service any time it's needed. Telguard puts nearly four decades of alarm communications expertise into every UL Listed communicator. You stay in control, with highly configurable options that meet your needs and the requirements of your AHJ. UL Listings(AT&T and Verizon) Specifications Size(without antenna) • 864 Commercial Fire Power Consumption 7.5 H x 11.5 W x 3.5 D in •1610 Central Station Standby: 18mA @ 24VDC (19.05 x 29.21 x 8.89 cm) 40mA @ 12VDC Available Accessories ULC Listings (AT&T Only) Transmit: 110mA @ 24VDC • High gain and directional antennas • S559 Commercial Fire 200mA @ 12VDC • Varying lengths of antenna cables • S304 Commercial Burglary • TG-PEM Power&Expansion Module Compatible Formats Certifications CID, SIA, Pulse(4x2,3x1), • California State Fire Marshal Radionics(Ile/3a2,4), DMP UMW I�O� -- • FDNY approval pending '®a co) I r� �o� CFSA r w••. Antenna: 5052 TNC connector(female) imiu � 1 CHOOSE THE COMMUNICATOR THAT BEST FITS THE NEEDS OF YOUR UPGRADE, TAKEOVER, OR NEW INSTALL PROJECT. FIRE PRODUCTS COMMUNICATION PATHWAYS INPUT POWER OPTIONS HARDWARE OPTIONS MODEL i CELLULAR INTERNET TELCO PANEL DC(12/24V) PLUG-IN AC UPGRADE BOARD TG-PEM 463j17.0 le TG-7FP d d TG-7FS d d 12V;24V needs TG-PEM d TG-7UBL For the most current product specifications and UL Listings visit telguard.com/tg-7fe.In Canada,cellular data may be carried by Rogers,Bell,Telus or SaskTel. 800.229.2326 13225 Cumberland Blvd SE•Suite 300•Atlanta,GA 30339•USA I telguard.com ©2021 Telguard I Telguard and the Telguard Logo are registered trademarks of Telular Corporation.I Telular is a business unit of AMETEK,Inc.All Rights Reserved. >`VIAETEIC 98 Pg.11 Ac SOB System Document Box f BY SPACE AGE ELECTRONICS SYSTEM RECORDS = FIR: DOCUMENTS =_ 4.1 OM% FEATURES A cost-effective answer for those looking for MpoE,Nusp Q Dimensions: 14 1/4"tall, 14 a durable, code-compliant enclosure to SlMM 1/3"wide and 3"deep ensure mandated records are maintained at Velcro strap and inside edge the fire alarm control unit location. keep important documents secure Every durable box is fabricated from 20 Standard thumb screw included with a knock-out if gauge steel with a powder coat finish and lock is needed features a formed lift-a-way hinge. Also (sold separately) included is a Velcro strap and inside edge to 20 gauge cold rolled steel keep important documents secure. construction with durable, red powder coat finish Lift-a-way hinge door for SPECIFICATIONS easy access The SDB System Document Box shall be constructed of 20 gauge cold rolled steel and finished with a durable, red powder coat. Front cover will feature a lift-a-way hinge. Door shall be secured with a standard thumb screw with a knock-out available if a lock is needed. Construction shall include a Velcro strap and inside edge to hold documents in place. Pg.99 Pg.12 ACEBOX DIMENSIONS 3.09 — 14.25 LIFT-A-WAY HINGE STYLE SYSTEM 1.25 RECORDS DOCUMENTS INCLUDED SCREW 14.00 14.25 1 .65 X.75 DIA `Optional IRF KNOCK-OUT IF Inspection Record Frame LOCK IS NEEDED (sold separately as1111 SSU00695 CAT30) P/Nassuszozol affixes SS00696 PK625) to front of box SSU00697 T45) 14.00 — lilt TERMINAL TERMINAL DUCT DUCT SS000691 SDB System Document Box CABINET CABINET DETECTOR DETECTOR FIRE FIRE EOL EOL J NCTTIION JUNCTION Accessories: BOX BOX FIRE FIRE ELEVATOR ELEVATOR SSU00695 CAT30 Lock kit ALARM ALARM CONTROL CONTROL CABINET CABINET SSU00696 PK625 Lock Kit FIRE CIRCU T INSIDE EMERGENCY SSU00697 T45 Lock Kit Inspection and Maintenance SSU03161 Inspection and Maintenance Identification Labels Identification Labels for verification SSU52020 IRF Inspection Record Frame per NFPA 72 Chapter 14(sold separately) www.lsae.com 1 toll free 1.800.486.1723 I fax 508.485.4740 f-1 Rig nE Iso ©Copyright 2018 Space Age Electronics, Inc.I This document subject to change without notice I LT10801 I Rev.A NFPA °�''' ADA P100 Pg.13 i w sERIEs Addressable Photoelectric Smoke Detectors The Silent Knight° SK-PHOTO-W Series feature a modern design and expanded color options support a variety of contemporary aesthetic demands. In addition, each detector is constructed for exceptional installation and maintenance efficiency. The SK-PHOTO-W Series intelligent plug-in smoke detectors are designed for both performance and aesthetics,and are direct replacements for the SK-PHOTO Series detectors.A new modern,sleek,contemporary design and enhanced optical sensing chamber is engineered to sense smoke produced by a wide range of combustion sources in accordance with more stringent code standards.The SK-PHOTO-W Series detector sensitivity can be programmed in the control panel software.Sensitivity is continuously monitored and reported to the panel.Point ID capability allows each detector's address to be set with rotary,decimal address switches,providing exact detector Location for selective maintenance when chamber contamination reaches an unacceptable level.Dual electronic thermistors add 135°F(57°C)fixed temperature thermal sensing on the SK-PHOTO-T-W. The SK-PHOTO-R-W is a remote test capable detector for use with DNR Series duct detector housings. FEATURES AND BENEFITS • Designed to meet UL 268 7th Edition • Integral communications and built-in • Expanded coLor options • SLeek and stylish contemporary design device-type identification • SEMS screws for wiring of the separate base • Stable communication technique with • Remote test feature from the paneL • OptionaL remote,single-gang LED noise immunity • Built-in functional test switch activated by accessory • Addressable by device external magnet • OptionaL sounder,relay,and isolator bases • Rotary,decimal addressing(Refer to the • WaLk test with address d351634ispLay(an Silent Knight paneL manuals for device address of 121 will blink the detector LED capacity) 12-(pause)-1) • Two-wire SLC connection • Low standby current • LEDs bLink every time the unit is polled • Built-in tamper-resistant feature • 360°-field viewing angle of the visual alarm • Designed for direct-surface or electrical- indicators(two bi-color LEDs);LEDs blink box mounting green in Normal condition and turn on • Sealed against back pressure Honeywell steady red in ALarm • Plugs into separate base for ease of installation and maintenance VI SILENT' Ida KNIGHT101 Pg.14 INSTALLATION B224BI-IV:Ivory,plug-in System Sensor isolator detector base The SK-PHOTO-W Series plug-in intelligentthermaldetectors use a ACCESSORIES separate base to simplify insta[[ation,service,and maintenance. Installation instructions are shipped with each detector. TR300:White,replacement flange for B210LP or B300-6 bases Mount base(al[base types)on an electrical backbox which is at TR300-IV:Ivory,replacement flange for B210LP or B300-6 bases least 1.5"(3.81 cm)deep.For a chart of compatible junction boxes, RA100Z(A):Remote 3-32 VDC LED annunciator,mounts to a U.S. see SK-61045. single-gang electrical box,for use with B501 and B300-6 bases Note:Because of the inherent supervision provided by the SLC loop, only end-of-line resistors are not required.Wiring"T-taps"or branches M02-04-00:Test magnet are permitted for Class"B"wiring. M02-09-00:Test magnet with telescoping handle Note:When using relay or sounder bases,consult the SK-ISO CK300:White,detector color kit,pack of 10 insta[[ation sheet 156-3627 for device[imitations between iso[ator CK300-IV:Ivory,detector co[or kit,pack of 10 modules and iso[ator bases. CK300-BL:Black,detector color kit,pack of 10 OPERATION Each SK-PHOTO-W Series detector uses one of the panel's addresses (total Limit is panel dependent)on the Signaling Line Circuit(SLC).It responds to regular polls from the control panel and reports its type and the status.If it receives a test command from the panel(or a local magnet test),it stimulates its electronics and reports an alarm.It blinks its LEDs when polled and turns the LEDs on when commanded by the panel.The SK-PHOTO-W Series offers features and performance that represent the Latest in smoke detector technology. PRODUCT LINE INFORMATION Note:"-IV"suffix indicates ivory co[or. SK-PHOTO-W:White,low-profile photoelectric sensor SK-PHOTO-T-W:White,same as SK-PHOTO-W but includes a built-in 135°F(57°C)fixed-temperature thermal device SK-PHOTO-R-W:White,low-profile intelligent photoelectric sensor, remote test capable,for use with DN R/DN RW B300-6:White,standard flanged low-profile mounting base B300-6-BP:Bulk pack of B300-6,package contains 10 B300-6-IV:Ivory,standard flanged low-profile mounting base B501-WHITE:White,standard European flangeless mounting base B501-BL:Black,standard European flangeless mounting base B501-IV:Ivory,standard European flangeless mounting base B501-WHITE-BP:Bu[k pack of B501-WHITE,contains 10 B200S-WH:White, Intelligent,programmable sounder base B200S-IV:Ivory,Intelligent,programmable sounder base B200SR-WH:White,Intelligent sounder base for retrofit applications B200SR-IV:Ivory,Intelligent sounder base for retrofit applications B200S-LF-WH:White,Low Frequency Intelligent,programmable sounder base B200S-LF-IV:Ivory,Low Frequency Intelligent,programmable sounder base B200SR-LF-WH:White,Low Frequency Intelligent sounder base for retrofit app[ications B200SR-LF-IV:Ivory,Low Frequency Intelligent sounder base for retrofit app[ications B224RB-WH:White,plug-in System Sensor°relay base B224RB-IV:Ivory,plug-in System Sensor relay base B224BI-WH:White,plug-in System Sensor isolator detector base Page 2 of 3—351634:C•5/28/2020 102 Pg.15 SK-PHOTO-W SERIES TECHNICAL SPECIFICATIONS PHYSICAL/ENVIRONMENTAL DETECTOR SPACING AND Sensitivity: APPLICATIONS Silent Knight°and System Sensor° 0 o Silent Knight recommends spacing are registered trademarks of -UL Applications:0.5/oto4.0/o per foot g Honeywell International, Inc. obscuration. detectors in compliance with NFPA72.In Low airflow applications with smooth ceiling, -ULC Applications:0.5%to 3.5%per foot space detectors 30 feet(9.1m). For specific This document is not intended to be obscuration information regarding detector spacing, used for installation purposes.We Size:2.0"(51mm)high;base determines placement,and special applications refer to try to keep our product information diameter N FPA 72.A System Smoke Detector up-to-date and accurate.We cannot -6300-6:6.1"(15.6 cm)diameter Application Guide,document SPAG91, cover all specific applications or available at www.systemsensor.com. -B501:4"(10.2 cm)diameter anticipate all requirements.All AGENCY LISTINGS AND specifications are subjectto change For a complete list of detector bases,see APPROVALS without notice. SK-61045. Shipping weight:3.4 oz.(95 g) These Listings and approvals apply to the Country of origin:Mexico modules specified in this document.ln some Operating temperature range: cases,certain modules or applications may • SK-PHOTO-W:32°F to 122°F(0°C to 50°C) not be Listed by certain approval agencies,or • SK-PHOTO-T-W:32°F to 100°F(0°C to Listing may be in process.Consult factory for 38°C) latest listing status. • SK-PHOTO-R-W installed in a DNR/DNRW: • UL Listed:S6173 -4°F to 158°F(-20°C to 70°C) • FM Approved • CSFM:7272-0559:0512 UL/ULC Listed Velocity Range:0-4000 ft/ min.(1219.2 m/min.),suitable for installation in ducts Relative humidity:10%—93°/o non- condensing Thermal ratings:fixed-temperature set point 135°F(57°C),rate-of-rise detection 15°F(8.3°C)per minute,high temperature heat 190°F(88°C) ELECTRICAL SPECIFICATIONS Voltage range:15-32 volts DC peak Standby current(max.avg.):200pA @ 24 VDC(one communication every 5 seconds with LED enabled) Max current:4.5 mA @ 24 VDC("ON") Honeywell Silent Knight 12 Clintonville Road Northford,CT 06472-1610 Honeywell 203.484.7161 351634 I c 05/20 SILENT' www.silentknight.com ©2020 Honeywell International Inc. ®KNIGHT' 103 Pg.16 i w SERIES Addressable Heat Detectors The Silent Knight° SK-HEAT-W Series heat detectors are designed for both performance and aesthetics. A new modern, sleek, contemporary design and advanced thermal technologies make the SK-HEAT-W Series ideal for both system operation and building - design. The series includes a 135°F/57°C fixed-temperature,rate-of-rise,and a 180°F/88°C fixed high-temperature detectors and are direct replacements for the SK-HEAT Series heat detectors.The point ID address,set using rotary decimaL switches,provide specific detector Locations.These thermaL detectors provide effective,intelligent property protection in a variety of applications. • SK-HEAT-W offers 135°F fixed thermaL detection. • SK-HEAT-ROR-W offers 135°F fixed and rate-of-rise thermal detection. • SK-HEAT-HT-W provides fixed high-temperature detection at 190°F. FEATURES AND BENEFITS • Designed to meet UL 268 7th Edition • 360°-field viewing angle of the visual alarm • Designed for direct-surface or electrical- • SLeek and stylish contemporary design indicators(two bi-coLor LEDs);LEDs blink box mounting • Advanced thermaL technology for fast green in Normal condition and turn on • Sealed against back pressure response steady red in Alarm • Plugs into separate base for ease of • Fixed temperature modeL(SK-HEAT-W) • IntegraL communications and built-in installation and maintenance factory preset to 135°F(57°C) device type identification • SEMS screws for wiring of the separate base • Rate-of-rise modeL(SK-HEAT-ROR-W), • Remote test feature from the paneL • OptionaL remote,single-gang LED 15°F(8.3°C)per minute • Built-in functional test switch activated by accessory • High temperature modeL(SK-HEAT-HT-W) external magnet • OptionaL sounder,relay,and isolator bases factory preset to 190°F(88°C) • Walk test with address display(an address • OptionaL flanged surface mounting kit • Addressable by device of 121 will blink the detector LED 12- • Rotary,decimaL addressing(Refer to the (pause)-1) Silent Knight paneL manuals for device • Low standby current capacity) • Built-in tamper-resistant feature Honeywell • Two-wire SLC connection • LEDs blink every time the unit is polled SILENT' ®KNIGHT104 Pg.17 APPLICATIONS B200SR-LF-IV:Ivory, Low Frequency Intelligent sounder base for Use thermal detectors for protection of property.For further retrofit applications information,refer to manual 156-6529,Applications Manual for B224RB-WH:White,plug-in System Sensor°relay base System Smoke Detectors,which provides detailed information on B224RB-IV:Ivory,plug-in System Sensor relay base detector spacing,placement,zoning,wiring,and special applications. B224BI-WH:White,plug-in System Sensor isolator detector base B224BI-IV:Ivory,plug-in System Sensor isolator detector base INSTALLATION The SK-HEAT-W Series plug-in intelligent thermal detectors use a ACCESSORIES separate base to simplify installation,service,and maintenance. TR300:White,replacement flange for B210LP or B300-6 bases Installation instructions are shipped with each detector. TR300-IV:Ivory,replacement flange for B210LP or B300-6 bases Mount base(al[base types)on an electrical backbox which is at RA100Z(A):Remote 3-32 VDC LED annunciator,mounts to a U.S. least 1.5"(3.81 cm)deep.Fora chart of compatible junction boxes, single-gang electrical box,for use with B501 and B300-6 bases see SK-61045. only Note:Because of the inherent supervision provided by the SLC loop, M02-04-00:Test magnet end-of-line resistors are not required.Wiring"T-taps"or branches are permitted for Style 4(Class"B")wiring. M02-09-00:Test magnet with telescoping handle Note:When using relay or sounder bases,consult the SK-ISO CK300:White,detector color kit,pack of 10 installation sheet 156-3627 for device limitations between isolator CK300-IV:Ivory,detector color kit,pack of 10 modules and isolator bases. CK300-BL:Black,detector color kit,pack of 10 PRODUCT LINE INFORMATION SK-HEAT-W:White,low-profile intelligent 135°F fixed thermal sensor SK-HEAT-ROR-W:White,low-profile intelligent rate-of-rise thermal sensor SK-HEAT-HT-W:White,low-profile intelligent 190°F fixed thermal sensor B300-6:White,standard flanged low-profile mounting base B300-6-BP:Bulk pack of B300-6,package contains 10 B300-6-IV:Ivory,standard flanged low-profile mounting base B501-WHITE:White,standard European flangeless mounting base B501-BL:Black,standard European flangeless mounting base B501-IV:Ivory,standard European flangeless mounting base B501-WHITE-BP:Bulk pack of B501-WHITE,contains 10 B200S-WH:White, Intelligent,programmable sounder base B200S-IV:Ivory,Intelligent,programmable sounder base B200SR-WH:White, Intelligent sounder base for retrofit applications B200SR-IV:Ivory,Intelligent sounder base for retrofit applications B200S-LF-WH:White,Low Frequency Intelligent,programmable sounder base B200S-LF-IV:Ivory,Low Frequency Intelligent,programmable sounder base B200SR-LF-WH:White,Low Frequency Intelligent sounder base for retrofit applications Page 2 of 3—351637:B•7/1/2019 105 Pg.18 SK-HEAT-W SERIES TECHNICAL SPECIFICATIONS PHYSICAL/ENVIRONMENTAL AGENCY LISTINGS AND Size:2.0"(5.3 cm)high;base determines APPROVALS Silent Knight°and System Sensor° diameter These listings and approvals apply to the are registered trademarks of -B300-6:6.1"(15.6 cm)diameter modules specified in this document.ln some Honeywell International, Inc. -B501:4"(10.2 cm)diameter cases,certain modules or applications may This document is not intended to be not be listed by certain approval agencies,or used for installation purposes.We For a complete list of detector bases,see listing may be in process.Consult factory for SK-61045. try to keep our product information latest listing status. up-to-date and accurate.We cannot Operating temperature range:SK HEAT W, • UL Listed:S6228 cover all specific applications or SK HEAT ROR W:-4°F to 100°F • FM Approved anticipate all requirements.All (-20°C to 38°C) • CSFM:7270-0559:0511 specifications are subject to change SK-HEAT-HT-W:-4°F to 150°F(-20°C to without notice. 66°C) Detector spacing:UL approved for 50 ft. Country of origin:Mexico (15.24 m)center to center;FM approved for 25 x 25 ft.(7.62 x 7.62 m)spacing Relative humidity:10%—93°/o non- condensing Thermal ratings:Fixed-temperature set point 135°F(57°C),rate-of-rise detection 15°F(8.3°C)per minute,high temperature heat 190°F(88°C) ELECTRICAL SPECIFICATIONS Voltage range:15-32 volts DC peak Standby current(max.avg.):200uA @ 24 VDC(one communication every 5 seconds with LED enabled) LED current(max.):4.5mA @ 24 VDC("ON") Honeywell Silent Knight 12 Clintonville Road Northford,CT 06472-1610 Honeywell 203.484.7161 351637 I B 107/19 SILENT' www.silentknight.com ©2019 Honeywell International Inc. ®KNIGHT 106 Pg.19 Honeywell ® SILENT' KNIGHT SK-PULL-SA / SK-PULL-DA Intelligent Pull Stations The SK-PULL-SA is a single action pull station requiring only one motion to activate the station.The SK-PULL-DA is a dual action pull station requiring F I R E two motions to active the station.The SK-PULL-SA and SK-PULL-DA are for use with Honeywell Silent Knight Series fire control panel(FACP). I PULL 1 DOPUWN 1 Extremely easy to operate,the SK-PULL-DA and SK-PULL-SA provide a fast and practical means of manually initiating a fire alarm signal.The FACP recognizes each manual pull station by its specific address saving precious seconds in determining the Location of an alarm. Honeywell z SING INSTALLATION a The SK-PULL-SA and SK-PULL-DA can be surface mounted to an SB-I/O SK-PULL-SA surface back box or semi-flush mounted on a standard single-gang with a minimum depth of 2.13"(5.40 cm)or double gang or 4"(10.61 cm)square - E electrical box.You can also use the optional(System Sensor°PN BG-TR) trim ring if the station is being semi-flush mounted. LIPULLDOWNIJ PUSH IN 1 Honeywell r5� - i• « I a SK-PULL-DA FEATURES & BENEFITS • Installer can open • Key operated test and • Meets the Americans • Reliable analog • Handle Latches in station without reset lock using lock with Disabilities Act communications for down position and the causing an alarm plate actuator Accessibility trouble-free operation word Activated condition Guidelines(ADAAG) appears,clearly • Key matches • Braille text on station • Dual-color LED is compatible FACP controls and operating handle indicating the station visible through handle locks mechanisms has been pulled guidelines(Section • Rotary address of station blinks green • Meets ADA 4.1.3[13]) switches for fast • U L Listed,including to indicate normal UL 38,Standard of requirement for 5 lbs installation operation and remains maximum pull force to • Shell,door,and handle Manually Actuated steady red in an alarm active molded from durable Signaling System condition LEXAN® • CSFM Listed • M EA Listed 107 Pg.20 SK-PULL-SA / SK-PULL-DA Technical Specifications Fora complete listing of all compliance approvals and certifications,please visit PHYSICAL ORDERING INFORMATION www.silentknight.com. Dimensions:5.5"H x 4"W x 1.45"D(14 x 10.2 x SK-Pull-SA:Single Action Pull Station Microsoft,3.7cm) SK-Pull-DA:Dua{ActionPullStation theWindoWindows,aend HousingMaterial:LEXAN of carbonate resin ste Windows Logos polycarbonate registered trademarks Bi-Colored LED: ACCESSORIES or trademarks of Blinking Green:Normal BG-TR:Optional trim ring. Microsoft Corporation. Steady Red:Alarm SB-I/O:Surface backbox,indoor/outdoor. Silent Knight®,System Switch:Single pole,single throw(SPST)normally *Unless otherwise noted,specifications apply to Sensor°and Honeywell® open(N/0)switch which closes upon activation of SK-Pull-SA and SK-Pull-DA are registered the pull station trademarks of Honeywell COMPATIBILITY International,Inc. ELECTRICAL The SK-PULL-SA AND SK-PULL-DA are This document is not Operating Voltage:15—32VDC compatible with the following Honeywell Silent intended to be used for SLC Standby and Alarm Current:350µA Knight fire alarm control panels: installation purposes.We z 6820:Addressable fire alarm control panel try to keep our product Wire Gauge:Up to 12AWG(3.1 mm ) information up-to 6820EVS:Addressable fire alarm control panel date and accurate.We ENVIRONMENTAL with an emergency voice system. cannot cover all specific Operating Temperature:32°F—120°F(0°C— 6808:Addressable fire alarm control panel applications or anticipate 49°C) 6700:Addressable fire alarm control panel all requirements.All specifications are subject Humidity:10%—93°/o non-condensing 5700:Addressable fire alarm control panel to change without notice. 5808:Addressable fire alarm control panel pport, 5820XL:Addressable fire alarm control panel call800or 446- 444. call 800-446-6444. 5820XL-EVS:Addressable fire alarm control panel with an emergency voice system For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 Doc 350135 I Rev E 111/17 SILENT' 800-328-0103 ©2017 Honeywell International Inc. ®KNIGHT 108 Pg.21 Honeywell ElSILENT' KNIGHT SK-MONITOR-2 Addressable Dual Monitor Module The SK-MONITOR-2 module is capable of monitoring two separate CLass B circuits simultaneously,making it ideal for waterflow tamper switch and flow switch monitoring. e • "O1esv The SK-MONITOR-2 is an addressable monitor module with two initiating circuits for use with Honeywell Silent Knight series fire alarm control panels "' _ •_ . (FACPs).The SK-MONITOR-2 acts as an interface to contact devices,such nw.. u=,•„ l: I. as water-Row switches and pull stations: iku MOOS uc wt..tame y ••�. ^- � 1.1 The SK-MONITOR-2 supports CLass B supervised wiring to the load device. Conventional 4-wire smoke detectors can be monitored for alarm and • trouble conditions.. 4Ik % • • INSTALLATION SK-MONITOR-2 mounts directly into a 4"square electrical box.The box SK-MONITOR-2 must have a minimum depth of 2-1/8".A surface mount electrical box (System Sensor®part number SMB500)is available from Silent Knight. FEATURES & BENEFITS • Monitor two circuits, • Panel controlled • Rotary address with unique status LED that switches for fast addresses, flashes green in installation simultaneously normal state and is • SEMS screws for easy • Support for Class B solid red in alarm wiring wiring • Attractive ivory cover • Fully supervised plate 109 Pg.22 SK-MONITOR-2 Technical Specifications + Fora complete listing of all To Next Device _ compliance approvals and n n certifications,please visit www.silentknight.com. y 0 O O Microsoft,Windows,and the Windows Logo are rz registered trademarks %*so MicrosofttrademarksCorporation. //�- Mooft Corpo [Q 0 eo 0 t% Silent Knight®,System Compatible FACP Two initiating device circuits NFPA U U Sensor°and Honeywell® Stlye B Power limited 230pA Max @ are registered 12VDC max SLC trademarks of Honeywell n n OUT IN International,Inc. 'b] NENE M7 This document is not °'� WU+ - intended to be used for re „ _ = ' installation purposes.We .� try toakeep our product information up-to v O o O date and accurate.We cannot cover all specific U U applications or anticipate all requirements.All Wiring SK-Monitor-2 Modules specifications are subject to change without notice. PHYSICAL AGENCY LISTINGS AND APPROVALS For TechnicalSupport, call 800-446-6444. Height:4.5"Hx4"Wx1.25"D ULListed Shipping Weight:6.3 oz(196 g) CSFM Approved City of New York Approved ELECTRICAL Operating Voltage:15—32 VDC COMPATIBILITY Standby and Alarm Current:750NA max @ 24VDC The SK-MONITOR-2 is compatible with the (one communication every 5 sec with 47K EOL) following Honeywell Silent Knight fire alarm End-of-Line Resistance:47KS2 control panels: 6820:Addressable fire alarm control panel ENVIRONMENTAL 6820EVS:Addressable fire alarm control panel Operating Temperature:32°F—120°F(0°C— with an emergency mass notification system. 49°C) 6808:Addressable fire alarm control panel Humidity:10%-93%non-condensing 6700:Addressable fire alarm control panel 5700:Addressable fire alarm control panel ORDERING INFORMATION 5808:Addressable fire alarm control panel SK-Monitor-2:Dual Monitoring Module 5820XL:Addressable fire alarm control panel ACCESSORIES. 5820XL-EVS:Addressable fire alarm control panel SMB500:4"Square Surface Mount Electrical Box with an emergency mass notification system. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 Doc 3501241 Rev E 11vr7 SILENT' 800-328-0103 ©2017 Honeywell International Inc. ®KNIGHT 110 Pg.23 Honeywell ®SILENT' KNIGHT SK-MONITOR Intelligent Monitor Module The SK-MONITOR is an addressable monitor module for use with Honeywell Silent Knight Series fire aLarm control panels(FACPs).The SK-MONITOR is intended for use in intelligent,two-wire systems,where individual address of each module is selected using the built-in rotary switches. The SK-MONITOR supports Class A supervised or Class B supervised • .,, wiring to the Load device.Conventional 4-wire smoke detectors can be monitored for alarm and trouble conditions. . - •� INSTALLATION The SK-MONITOR mounts directly into a 4"square electrical box.The box must have a minimum depth of 2-1/8".A surface mount electrical box (System Sensor®PN SMB500)is available from Silent Knight. SK-MONITOR FEATURES & BENEFITS • Single contact monitor • Panel controlled • UL Listed • Support for Class A status LED that • Rotary address and Class B wiring flashes green in switches for fast normal state and is installation • Fully supervised solid red in alarm • SEMS screws for easy wiring 111 Pg.24 SK-MONITOR Technical Specifications Fora complete listing of all compliance approvals and certifications,please visit PHYSICAL ORDERING INFORMATION www.silentknight.com. Height:4.5"H x 4"Wx 1.25"D(11.4X 10.2 X 3cm) SK-MONITOR:Monitor Module Microsoft,Windows,and Shipping Weight:6.3 oz(196 g) the Windows Logo are ACCESSORIES. registered trademarks ELECTRICAL SM6500:4"Square surface mount electrical box or trademarks of Operating Voltage:15—32VDC Microsoft Corporation. Current Draw(LED on):5.0mA max COMPATIBILITY The SK-MONITOR is compatible with the Silent Knr®an t ,Hotem neywell® Operating Current(LED flashing):375µA p Sensor®and Honeywell Standby Current:400 µA max 24 VDC(one following Honeywell Silent Knight fire alarm are registered communication every 5 sec with 47K EOL);550 µA control panels: trademarks of Honeywell 6820:Addressable fire alarm control panel International,Inc. max®24 VDC(one communication every 5 sec with EOL<1K) 6820EVS:Addressable fire alarm control panel This document is not 5.5 mA(with LED latched on) with an emergency mass notification system. intended to be used for LED Current:5.5 mA(with LED latched on) 6808:Addressable fire alarm control panel installation purposes.We End-of-Line Resistance:47K Q 6700:Addressable fire alarm control panel try to keep our product information up-to Initiating Device Circuit Wiring Resistance:1,500 5700:Addressable fire alarm control panel date and accurate.We S2max 5808:Addressable fire alarm control panel cannot cover all specific SLC Loop Resistance:40 12 max. 5820XL:Addressable fire alarm control panel applications or anticipate all requirements.All ENVIRONMENTAL 5820XL-EVS:Addressable fire alarm control panel specifications are subject with an emergency mass notification system to change without notice. Operating Temperature:32°F—120°F(0°C— 49°C) For TechnicalSupport, Humidity:10%-93%non-condensing call 800 446 6444. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 Doc 3501311 Rev G 11/17 SILENT' 800-328-0103 ©2017 Honeywell International Inc. ®KNIGHT 112 Pg.25 Honeywell ElSILENT' KNIGHT SK-MINIMON Intelligent Mini Monitor Module The SK-MINIMON is an addressable monitor modules for use with the Honeywell Silent Knight fire alarm control panels(FACPs).The SK- MINIMON acts as an interface to contact devices,such as waterflow switches and pull stations.The SK-MINIMON supports Class B supervised wiring to the Load device.Conventional 4-wire smoke detectors can be .. monitored for alarm and trouble conditions The SK-MINIMON can be mounted in a single gang junction box directly • behind the monitored device.Its small size and lightweight allow it to be installed without rigid mounting requirements. SK-MINIMON INSTALLATION The SK-MINIMON can be mounted in a single gang junction box directly behind the monitored device.Its small size and lightweight allow it to be installed without rigid mounting requirements. FEATURES & BENEFITS • Single contact monitor • Rotary address • SK-Minimon support switches for fast for Class B(Style B) installation contact monitor wiring • UL Listed • Small and lightweight • CSFM Listed size allows for flexible • FM Approved mounting options 113 Pg.26 SK-MINIMON Technical Specifications Fora complete listing of all compliance approvals and certifications,please visit PHYSICAL ORDERING INFORMATION www.silentknight.com. Dimensions:2.75"W x 1.3"H x 0.5"D SK-MINIMON:Mini monitoring module Microsoft,Windows,and Weight:1.2 oz(37 g) COMPATIBILITY the Windows Logo are registered trademarks ELECTRICAL The SK-M IN I MON is compatible with the or trademarks of Operating Voltage:15—32VDC following Honeywell Silent Knight fire alarm Microsoft Corporation. SLC Standbyand Alarm Current:350 A control panels: µ 6820:Addressable fire alarm control panel Silent Knight®,System End-of-Line Resistance:47KSZ p Sensor°and Honeywell® Initiating device circuit wiring resistance:1,50052 6820EVS:Addressable fire alarm control panel are registered max with an emergency voice system. trademarks of Honeywell SLC loop resistance:40E2 max 6808:Addressable fire alarm control panel International,Inc. Wire Length:6"min. 6700:Addressable fire alarm control panel This document is not 5700:Addressable fire alarm control panel intended to be used for ENVIRONMENTAL 5808:Addressable fire alarm control panel installation purposes.We try to keep our product Operating Temperature:32°F—120°F(0°C— 5820XL:Addressable fire alarm control panel information up-to 49°C) 5820XL-EVS:Addressable fire alarm control panel date and accurate.We Humidity:10%-93%non-condensing with an emergency voice system cannot cover all specific applications or anticipate all requirements.All specifications are subject to change without notice. For TechnicalSupport, call 800-446-6444. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 Doc 350133 I Rev G 111/17 SILENT' 800-328-0103 ©2017 Honeywell International Inc. ®KNIGHT 114 Pg.27 Honeywell ® SILENT' KNIGHT SK-RELAY Intelligent Relay Module The SK-RELAY is an addressable relay module for use with Honeywell Silent Knight Series fire alarm control panels(FACPs).The SK-RELAY allows a Silent Knight FACP to switch discrete contacts by code command.The relay contains two isolated sets of Form C contacts,which operate as a DPDT switch.No supervision is provided for the notification appliance circuit. Honeywell r The SK-RELAY contacts can be used for virtually any normally open or siii�u:�u,frr normally closed application.Each SK-RELAY is programmed with a unique signaling line circuit(SLC)Loop address.When an event occurs that controls the SK-RELAY,the relay is triggered by the FACP. • INSTALLATION l The SK-RELAY mounts directly into a 4"square electrical box.The box must SK-RELAY have a minimum depth of 2-1/8".A surface mount electrical box(System Sensor°PN SMB500)is available from Silent Knight. FEATURES & BENEFITS • Two sets of Form C • Panel controlled • Polling LED visible contacts status LED that through the cover • Rotary address flashes green in plate switches for fast normal state and is • SEMS screws for easy installation solid red in alarm wiring • Contacts are rated for • Relay programming is • UL Listed a variety of amps(see completely flexible- Specifications) can be mapped to zone conditions 115 Pg.28 SK-RELAY Technical Specifications Fora complete listing of all compliance approvals and certifications,please visit PHYSICAL ORDERING INFORMATION www.silentknight.com. 4.675"H x 4.275"W x 1.4"D SK-RELAY:Relay Module Shipping Weight:6.3 oz(196 g) Microsoft,Windows,and the Windows Logo are ACCESSORIES. registered trademarks ELECTRICAL SMB500:4"Square Surface Mount Electrical Box or trademarks of Operating Voltage:15—32 VDC CB500:Module Barrier Microsoft Corporation. End-of-Line Resistance:Not used Silent Knight®,System SLC Standby&Alarm Current:.255mA max® COMPATIBILITY Sensor°and Honeywell® 24VDC(one communication every 5 sec with LED The SK-RELAY is compatible with the following are registered enabled) Honeywell Silent Knight fire alarm control panels: trademarks of Honeywell 6820:Addressable fire alarm control panel International,Inc. ENVIRONMENTAL 6820EVS:Addressable fire alarm control panel This document is not Operating Temperature:32°F—120°F(0°C— with an emergency mass notification system. intended to be used for 49°C) 6808:Addressable fire alarm control panel installation purposes.We Humidity:10%—93°/o non-condensing 6700:Addressable fire alarm controlpanel try to keep our product information up-to RELAY CONTACT RATINGS 5700:Addressable fire alarm control panel date and accurate.We 5808:Addressable fire alarm control panel cannot cover all specific 3.0A®30VDC resistive applications or anticipate 0.9A 110VDC resistive 5820XL:Addressable fire alarm control panel all requirements.All 0.9A 125VAC resistive 5820XL-EVS:Addressable fire alarm control panel specifications are subject with an emergency mass notification system. to change without notice. 0.5A @ 125VAC inductive(PF=.35) 0.7A @ 75VAC inductive(PF=.35) For TechnicalSupport, call 800-446-6444. For more information Learn more about Honeywell Silent Knight and other products by visiting www.silentknight.com Honeywell Silent Knight 12 Clintonville Road Honeywell Northford,CT 06472 Doc 3501271 RevGI 11/17 SILENT' 800-328-0103 ©2017 Honeywell International Inc. ®KNIGHT 116 Pg.29 ov.-9,100 • VO 1ITPV'f !�TVr'i?ogRn •protects dedicated 120VAC power " ' ` circuits that feed control panels and other critical equipment. The % .46 ""�� .� , hybrid, series-wired design provides maximum critical load % j ,. } " �" " protection, and includes dry contacts for remote notification of surge protection status. EMI/RFI filtering ensures clean power for % connected equipment. irov • Produr retfures Techn �..,, a ecification ,, Series-wired design for fast response and best I 120VAC Single cD level of protection Voltage Configuration: (2W+G) Compact design fits a variety of control panels MCOV: 150V Multi-stage hybrid circuit design Protection Modes: L-N, L-G, N-G UL1283 EMI/RFI filtering 600V L-G, L-N Voltage Protection Rating: 1000V N G Diagnostic LED provides positive indication of 1 system power and SPD function Surge Current Rating: 50,000A AI Form C dry contacts for remote monitoring Max Continuous Current: 20A SCCR: 10,000A ■ Applir tions Nominal Discharge 4 Fire Alarm Panels Current Rating(In): 10kA Control Panels Operating Frequency: 50/60Hz 11 120VAC Single Phase Critical Loads EMI/RFI Filtering Up to 35dB, 100kHz—100MHz UL Listed Control Panels where UL Attenuation: Recognized Components are Required I Connection Method: Hardwired studs,series-wired I Accessories DIN Rail Mounting Kit, p/n DTK-DRK Housing: ABS Operating Temperature: -32°F—104°F(0°C—40°CJ Maximum Humidity: 95% non-condensing 7 Dimensions: 6.87" L x 3.5"W x 2.5" H (174.5mmx89mmx63.5mm) Weight: 12.16 oz(0.35 kg) ' Quality Standards &Ap.royal Certifications: M_ UL1449 4th Edition, UL1283 SPD Type: Type 2 Component Assembly Warranty: 10 Year Limited Warranty 117 Pg.30 �� SYSTEM `�~` �$ SENSOR® i . ., L-Series and L-Series with LED . - .r, Indoor Selectable F F F F rr I E E •F Horns, Strobes andI Horn Strobes ``-'� F System Sensor L-Series and L-Series with LED audible visible notification products are rich with features rr guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. {' Features The System Sensor L-Series and L-Series with LED • LED technology provides lower current draw platform offers the most versatile and easy-to-use line of horns, • Digital Voltage Meter(DVM)diagnostic test points for Horn strobes,and horn strobes in the industry with lower current draw and Strobes and Strobes modern aesthetics. LED lighting technology offers significantly lower • Common aesthetics across the L-Series platform current draw compared to older Xenon bulbs across a full candela • Standard and compact sizes range.This improves design flexibility for notification appliance • Tamper-resistant construction circuits(NACs)while also reducing power supply requirements • Field-selectable candela settings on wall units: 15,30,75,95, allowing for simpler and lower cost installations. 110, 135,and 185 Flexible design options meet virtually any application requirement: • Field-selectable candela settings on ceiling units: 15,30,75,95, wall or ceiling mount,standard or compact sizes,red or white color 115, 150,and 177 choices, bezel kits for alternate markings and languages, and LED • Rotary switches for candela,tone and volume selections color lenses for distinctive visual signaling. In addition, installers can • Mounting plate provides plug-in design for easier installation and easily adapt devices using field selectable candela,tone and volume shorting springs to check wiring continuity settings using rotary switches. • Electrically compatible with legacy SpectrAlert,SpectrAlert Advance and L-series devices The L-Series and L-Series with LED line is developed to simplify • Synchronization through use of UL approved power supplies that installation.All devices feature plug-in designs with minimal intrusion support System Sensor Sync protocol or System Sensor MDL3 into the back box,making installations fast and foolproof while Sync Module virtually eliminating costly and time-consuming ground faults.The • Horns,Strobes and Horn Strobes listed for wall or ceiling use universal mounting plate includes an onboard shorting spring,so installers can test wiring continuity before the device is installed. In addition,the System Sensor L-Series with LED notification Agency Listings appliances offer a new diagnostic test point feature that allows you to measure device voltage with a digital voltage meter(DVM)without SIGNALING SIGNALING ! ! removing the appliance from the wall or ceiling.The DVM test points C OuS13 CI ® © are discreetly located on the face of the notification appliance which LISTED LISTED LISTED APPROVED Ill enable faster troubleshooting and end of line(EOL)voltage checks Horn Strobes Horns: Horns: 3057072 7300-1653:0525 while greatly reducing the risk of misplacing or damaging appliances and Strobes: 54011 S4011 FM23FPUS0195 7135-1653:0503 S5512,S4011 7135-1653:0526 during troubleshooting. AVDS916-01•10/03/2023•Page 1 118 Pg.31 L-Series and L-Series with LED Specifications Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage,LED Strobes and Horn Strobes Regulated 24 VDC Nominal Voltage,Horns Regulated 12 VDC or regulated 24 DC/FWR Operating Voltage Range,LED Strobes and Horn Strobes 16 to 33 V(24 V nominal) Operating Voltage Range,Horns 8 to 17.5 V(12 V nominal)or 16 to 33 V(24 V nominal) Input Terminal Wire Gauge 12 to 18 AWG UWLC Current Draw Data, Horn Tones,and Sound Output Data UL/ULC Maxmimum Strobe Current Draw(mA) UWLC Maxmimum Horn Current Draw(mA RMS) Candela 16-33 Volts 8-17.5 Volts 16-33 Volts Rating Wall Ceiling Sound Pattern dB DC DC FWR Candela 15 18 18 Temporal High 39 44 54 Range 30 22 22 Temporal Low 28 32 54 75 70 70 Non-Temporal High 43 47 54 95 75 75 Non-Temporal Low 29 32 54 110 85 — 3.1 KHz Temporal High 39 41 54 115 — 90 3.1 KHz Temporal Low 29 32 54 135 105 — 3.1 KHz Non-Temporal High 42 43 54 150 — 110 3.1 KHz Non-Temporal Low 28 29 54 177 — 115 Coded High 43 47 54 185 120 — 3.1 KHz Coded High 42 43 54 UL/ULC Maximum Horn Strobe Current Draw(mA)and Sound Output(dBA) Current Draw(mA RMS),Horn Strobe, Sound Candela Range(15-185 cd) Output (dBA) 16-33 Volts 16-33V Switch Volume 15cd 30cd 75cd 95cd 110cd 115cd 135cd 150cd 177cd 185cd DC Pos. Sound Pattern Setting WALL CEILING WALL CEILING CEILING WALL 1 Temporal3 High 35 38 87 92 94 120 189 189 190 190 87 2 Temporal3 Low 35 38 87 92 94 120 135 135 145 145 79 3 Non-Temporal High 50 52 87 92 94 120 127 127 135 135 87 4 Non-Temporal Low 35 38 87 92 94 120 125 125 130 130 79 5 3.1 KHz Temporal 3 High 35 38 87 89 91 115 155 155 165 165 86 6 3.1 KHz Temporal 3 Low 35 38 87 89 91 115 128 130 135 135 80 7 3.1 KHz Non-Temporal High 40 42 87 89 91 115 125 125 135 135 86 8 3.1 KHz Non-Temporal Low 35 38 87 89 91 115 120 120 130 130 80 AVDS916-01•10/03/2023•Page 2 119 Pg.32 L-Series with LED Dimensions:Wall-Mounted Equipment 2.07" — 3.46" — —3.46"— (53 mm) 88 mm — — 1.25" 3.57" 1.55" 88mm 125 32mm (9.1 cm) (3.9 cm) (31.8 mm) 0.0.0.0.0.00`0 V ; 0 1 �I ®1 0o0°0oi (I 0°6°n°0°0°6°n, -- LL 5.27, �, o°o°°°°°°00°0 5.38" �C G I1-- pall'p 5.27" ������. 13.7 em 133.9mm 133.9 mm j 1 ( ) u O Tile- o jljljljlelj A0617-00 A0547-00 A0557-00 Compact Strobe,Horn Strobe Compact Horn Compact Surface Mount Back Box for Wall for Walls(SBBGRL,SBBGWL) 2.07' .7" 4.T 53.8m) — H 1.25" .4 119 mm 1.25' 119 mm 32 mm 1.85" (31.8 mm) (14.8"cm) / ii / H III\ 0° (4.69 cm) °00o lll...rrr ® , 144 mm np 5.67" " w w 5.78" 41_.�` 144 mm .1".."1 (14.68 cm) O II J ,. 1 1 1 11 1 \ y .o.o — 1�1i1i111i1 !. 1 111 (I `� :Jl ® !I 1f� A0613-00 A0549-00 A0554-01 Strobes,Horn Strobes Horn Surface Mount Back Box for Walls for Walls(SBBRLJSBBWL) L-Series with LED Dimensions: Ceiling-Mounted Equipment 6.92- 2.07 175.7iam. 2.m (52.6m mm) (75.77 mm) (64 mm) 6.83"dam. - 1.25" (173.5 mm) (31.8 mm) a _ L_, 11 i1. - 1p,, 8 0 °8 eWW ms_ �� A0608-00 A0546-00 Strobes and Horn Strobes Surface Mount Back Box for Ceilings for Ceilings(SBBCRL,SBCWL) AVDS916-01•10/03/2023•Page 3 120 Pg.33 L-Series with LED: Ordering Information Model Description IME Model Description L-Series with LED Horn Strobes LED Lenses P2RLED 2-Wire,Horn Strobe,Wall,Red LENS-A3 Lens LED Amber Wall/Ceiling P2RLED-B 2-Wire,Horn Strobe,Wall,Red,Bilingual LENS-B3 Lens LED Blue Wall/Ceiling P2WLED 2-Wire,Horn Strobe,Wall,White LENS-G3 Lens LED Green Wall/Ceiling P2WLED-B 2-Wire,Horn Strobe,Wall,White,Bilingual LENS-R3 Lens LED Red Wall/Ceiling P2GRLED 2-Wire,Compact Horn Strobe,Wall,Red Accessories P2GRLED-B 2-Wire,Compact Horn Strobe,Wall,Red,Bilingual TR-2 Universal Wall Trim Ring Red P2GWLED 2-Wire,Compact Horn Strobe,Wall,White TR-2W Universal Wall Trim Ring White P2GWLED-B 2-Wire,Compact Horn Strobe,Wall,White, SBBRL Wall Surface Mount Back Box,Red Bilingual SBBWL Wall Surface Mount Back Box,White P2RLED-P 2-Wire,Horn Strobe,Wall,Red,Plain SBBGRL Compact Wall Surface Mount Back Box,Red P2WLED-P 2-Wire,Horn Strobe,Wall,White,Plain SBBGWL Compact Wall Surface Mount Back Box,White P2RLED-SP 2-Wire,Horn Strobe,Wall,Red,FUEGO TRC-2 Universal Ceiling Trim Ring,Red P2WLED-SP 2-Wire,Horn Strobe,Wall,White,FUEGO TRC-2W Universal Ceiling Trim Ring,White PC2RLED 2-Wire,Horn Strobe,Ceiling,Red SBBCRL Ceiling Surface Mount Back Box,Red PC2RLED-B 2-Wire,Horn Strobe,Ceiling,Red,Bilingual SBBCWL Ceiling Surface Mount Back Box,White PC2WLED 2-Wire,Horn Strobe,Ceiling,White Bezelst PC2WLED-B 2-Wire,Horn Strobe,Ceiling,White,Bilingual BZR Wall Red Bezel Kit L-Series with LED Strobes BZW Wall White Bezel Kit SRLED Strobe,Wall,Red BZGR Compact Wall Red Bezel Kit SRLED-B Strobe,Wall,Red,Bilingual BZGW Compact Wall White Bezel Kit SWLED Strobe,Wall,White BZRC Horn Strobe Ceiling Red Bezel Kit SWLED-B Strobe,Wall,White,Bilingual BZWC Horn Strobe Ceiling White Bezel Kit SGRLED Strobe,Compact,Wall, Red SGRLED-B Strobe,Compact,Wall, Red, Bilingual Notes for L-Series With LED Horn Strobes and Strobes: SGWLED Strobe,Compact,Wall,White All-P models have a plain housing(no"FIRE"marking on cover). All-SP models have"FUEGO"marking on cover. SGWLED-B Strobe,Compact,Wall,White,Bilingual All-ALERT models have"ALERT"marking on cover. SRLED-P Strobe,Wall,Red,Plain All-B models have"FIRE/FEU"marking on cover for use in Canadian SWLED-P Strobe,Wall,White,Plain applications. SRLED SP Strobe,Wall,Red,FUEGO Amber lenses are not for use in Canadian applications SWLED-CLR- Strobe,Wall,White,ALERT Notes for L-Series Horns: ALERT "Horn-only models are listed for wall or ceiling use. SWLED-ALERT Strobe,Wall,White,ALERT,Amber Lens SCRLED Strobe,Ceiling,Red Notes for Bezels: SCRLED-B Strobe,Ceiling,Red,Bilingual tEach bezel pack ships in a package of 5. Add one of the following extensions for print/language options:-F(FIRE),-AL SCRLED-P Strobe,Ceiling,White,Plain (ALERT),-EV(EVAC),-AG(AGENT),-P(Plain),-FR(FEU),-PG(FOGO),-SP SCWLED Strobe,Ceiling,White (FUEGO),-SPE(FUEGO/FIRE). SCWLED-B Strobe,Ceiling,White,Bilingual SCWLED-P Strobe,Ceiling,White,Plain SCWLED-CLR- Strobe,Ceiling,White,ALERT ALERT L-Series Horns HRL" Horn,Red HRLA" Horn,Red,Plain,ULC HWL* Horn,White HWLA* Horn,White, Plain,ULC HGRL" Compact Horn, Red HGRLA" Compact Horn, Red, Plain,ULC HGWL* Compact Horn,White HGWLA" Compact Horn,White,Plain, ULC 3825 Ohio Avenue•St.Charles, IL 60174 USA System Sensor®is a registered trademark Phone:800-SENSOR2•Fax:630-377-6495 of Honeywell International,Inc. www.systemsen sor.com *T SYSTEM 3333 Unity Drive, Mississauga, ON L5L 3S6 Canada ©2023 System Sensor. � SENSOR® Phone:800-SENSOR2•Fax:905 812 0771 Product spepBoauic inform aottochangewih ltestivesion thisdatasheet. for current product information,including the latest version of this data sheet. www.systemsensor.ca AVDS916-01.10/03/2023 121 Pg.34 *Th SYSTEM �$ SENSOR® 41: !'0 L-Series Speakers _ _ and L-Series with LED '"" Speaker Strobes4 -' rJi�ir►4 frrr, 11011 rrrrrlf 1 + System Sensor L-Series and L-Series with LED audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Features The System Sensor L-Series and L-Series with LED • LED technology provides lower current draw platform offers the most versatile and easy-to-use line of speakers • Digital Volt Meter(DVM)diagnostic test points for Speaker and speaker strobes in the industry with lower current draw and Strobes modern aesthetics. LED lighting technology offers significantly lower current draw compared to older Xenon bulbs across a full candela • Common aesthetics across the L-Series platform range.This improves design flexibility for notification appliance • Tamper-resistant construction circuits(NACs)while also reducing power supply requirements • Field-selectable candela settings on wall units: 15,30,75,95, allowing for simpler and lower cost installations. 110, 135,and 185 • Field-selectable candela settings on ceiling units: 15,30,75, Flexible design options meet virtually any application requirement: 95, 115, 150,and 177 wall or ceiling mount,red or white color choices,bezel kits for • Rotary switches for candela,speaker voltage(25 and 70.7 alternate markings and languages,and LED color lenses for Vrms)and power settings(IA,1/2, 1,and 2 watts) distinctive visual signaling. In addition, installers can easily adapt • Mounting plate provides plug-in design for easier installation devices using field selectable candela, using rotary switches. and shorting springs to check wiring continuity The[-Series and L-Series with LED line is developed to simplify • Electrically compatible with legacy SpectrAlert,SpectrAlert installation.All devices feature plug-in designs with minimal intrusion Advance and[-series devices at 16-33 VDC into the back box,making installations fast and foolproof while • Synchronization through use of UL approved power supplies virtually eliminating costly and time-consuming ground faults.The that support System Sensor Sync protocol or System Sensor universal mounting plate includes an onboard shorting spring,so MDL Sync Module installers can test wiring continuity before the device is installed. • Speakers and Speaker strobes listed for wall or ceiling use • No extension ring required The low harmonic distortion of the speaker offers high fidelity sound • Speakers offer high fidelity and high volume sound output output while offering high volume sound output for use in high ambient noise applications. • 520 Hz capable with compatible Fire alarm control panel(FACP) In addition,the System Sensor L-Series with LED notification appliances offer a new diagnostic test point feature that allows you to measure device voltage with a digital voltage meter(DVM)without removing the appliance from the wall or ceiling.The DVM test points Agency Listings are discreetly located on the face of the notification appliance which enable faster troubleshooting and end of line(EOL)voltage checks SIGNALING weirs while greatly reducing the risk of misplacing or damaging appliances TO CO US cOus ® ( during troubleshooting. LISTED LISTED APPROVED h v .I Speaker-Strobes: Speakers: Speakers: 3057383 7125-1653:0533 S4048 S4048 S4048 3057493 7135-1653:0532 7320-1653:0505 AVDS-62174:A•08/29/2024•Page 1 122 Pg.35 Product Specifications Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F(0°C to 49°C) Humidity Range 10 to 93%non-condensing Power 1/4,1/2, 1,2 Watts Frequency Range 400 to 4000 Hz Maximum Supervisory Voltage(Speakers) 50 VDC Maximum Supervisory Voltage(Strobe) 33 VDC Strobe Flash Rate 1 Flash Per Second Nominal Voltages,Speakers 25 Volts or 70.7 Volts(nominal) Nominal Voltage,Strobe Regulated 24 VDC Operating Voltage Range,Strobe 16 to 33 VDC Input Terminal Wire Gauge 12 to 18 AWG Dimensions Wall Speaker Strobes(including lens) 6.5"L x 5.00" W x 2.3" D (165.1mm L x 127mm W x 58.4mm D) Wall Speaker Strobes(including lens)with SBBSPRUWL Surface 6.62"L x 5.12"W x 4.55"D(168.1mm L x 130mm W x 115.5mm D) Mount Back Box Ceiling Speaker Strobes(including lens) 6.8"diameter x 2.33"D(172.7mm x 59.2mm) Ceiling Speaker Strobes(including lens)with SBBCRUWL Surface 6.9"diameter x 4.83"D(176mm x 122.7mm) Mount Back Box Wall SPL Speakers 6.5"L x 5.00"W x 0.97"D(165.1mm L x 127mm W x 23mm D) Wall Speakers with SBBSPRUWL Surface Mount Back Box 6.62"L x 5.12"W x 3.2"W(168.1mm x 130mm x 81.2mm) Ceiling SPC Speakers 6.8"diameter x 1.0"D(173mm x 25mm) Ceiling Speakers with SBBCRUWL Surface Mount Back Box 6.9"diameter x 3.5"D(176mm x 89mm) NOTE:SBBSPRL/WL Surface Mount Back Box intended for speaker strobes and speakers. Minimum Speaker Strobe Sound Output /aW 1/zW 1 W 2W UL Reverberant(dBA @10 ft) 76 79 82 83 UL Anechoic(dBA @10 ft) 76 79 82 83 Minimum Speaker Only Sound Output 1/a ° 1/z W 1 W UL Reverberant(dBA @10 ft) 79 82 85 88 UL Anechoic(dBA @10 ft) 79 82 85 88 UL/ULC Maximum Strobe Current Draw(mA) UUULC Max Strobe Current Draw (mA RMS) Candela Rating 16 to 33 Volts DC 15 18 30 22 75 70 95 75 110 85 115 90 135 105 150 110 177 115 185 120 FCP* (future) *FCP Fire Control Panel,future use AVDS-62174:A•08/29/2024•Page 2 123 Pg.36 L-Series Dimensions [127] 0.97" _ __ = 1.63" f 1.II 5" (24.64 mm) (41.66 mm) 143,4] _ (127 mm) I � _ li41 U-1uDos'p°i pp °Oeee®09Oip9O90a p o? / / pppBO A.B.B e B B A .a0000 1� �...;;..'\,,►/ / gp A DOggp000o0.0.O00p0 ®®'0 ogj 1 OF goo I� °40 °' .p® �11 1A4O o =P ID 6.5" _ II I 6.se gall pop, \ % ago oleo 1. ID � M 80/00 ��00o/B 1 p (165 mm) 6s,1] o0 0 og0g0gogoo0o0gog0gog0 00 0 110E 0010 D0ap0/080/0800ap00ap0 poop [Omni -I 0000 000000000000000000000 Opp VI pop0 1/80108041 00pp00pp0 pp0g OOBf po ,.,op0pop0,o 0pop0po,, op AB II � u'�-�� NI A0555-01 O A0648-00 Wall-Mount Speaker Wall-Mount Speaker Strobe 159,11 6 — Q6so [aa.]] (173mm) (25.4 mm) 811.66mm) FM ;1 ., ir,r1) :-. I` ; M=II L-Series with LED: Surface Mount Back Box ®\ 41111 #f. ' H, 41) 1 ri,.... Ilk elh ' , ( ,,,, — , NI,N.A__,-- y___ _ s ,, ' triik6_,41111'1/.; % (/-1.r," ),,i .,1 , � A r�, : :�al �i 1 11 I,,,1 _... ....-1Alk s 1,-_-_-_ ---2-, , . . , i,---:..... , .., ) A0649-00 A0650-00 Wall-Mount Speaker Strobe with Ceiling-Mount Speaker Strobe with SBBSPSRUSBBSPWL Surface Mount Back Box SBBCRUSBCWL Surface Mount Back Box AVDS-62174:A•08/29/2024•Page 3 124 Pg.37 L-Series with LED: Ordering Information Model Description L-Series with LED Speaker Strobes SPSCRLED 2-WIRE,SPEAKER STROBE LED RED CEILING SPSCRLED-B 2-WIRE,SPEAKER STROBE LED RED CEILING BILINGUAL SPSCRLED-BT 2-WIRE,SPEAKER STROBE LED RED CEILING BILINGUAL WITH TRIM SPSCWLED 2-WIRE,SPEAKER STROBE LED WHITE CEILING SPSCWLED-B 2-WIRE,SPEAKER STROBE LED WHITE CEILING BILINGUAL SPSCWLED-BT 2-WIRE,SPEAKER STROBE LED WHITE CEILING BILINGUAL WITH TRIM SPSCWLED-T 2-WIRE,SPEAKER STROBE LED WHITE CEILING WITH TRIM SPSCWLED-TP 2-WIRE,SPEAKER STROBE LED WHITE CEILING PLAIN WITH TRIM SPSCWLED-CLR-ALERT 2-WIRE,SPEAKER STROBE LED WHITE CEILING ALERT CLEAR LENS SPSCWLED-P 2-WIRE,SPEAKER STROBE LED WHITE CEILING PLAIN SPSCWLED-SP 2-WIRE,SPEAKER STROBE LED WHITE CEILING FUEGO SPSRLED 2-WIRE,SPEAKER STROBE LED RED WALL SPSRLED-B 2-WIRE,SPEAKER STROBE LED RED WALL BILINGUAL SPSRLED-P 2-WIRE,SPEAKER STROBE LED RED WALL PLAIN SPSRLED-SP 2-WIRE,SPEAKER STROBE LED RED WALL FUEGO SPSWLED 2-WIRE,SPEAKER STROBE LED WHITE WALL SPSWLED-B 2-WIRE,SPEAKER STROBE LED WHITE WALL BILINGUAL SPSWLED-ALERT 2-WIRE,SPEAKER STROBE LED WHITE WALL ALERT AMBER LENS SPSWLED-CLR-ALERT 2-WIRE,SPEAKER STROBE LED WHITE WALL ALERT CLEAR LENS SPSWLED-P 2-WIRE,SPEAKER STROBE LED WHITE WALL PLAIN L-Series Speaker Description SPCRL 2-WIRE,SPEAKER RED CEILING SPCWL 2-WIRE,SPEAKER WHITE CEILING SPRL 2-WIRE,SPEAKER RED WALL SPWL 2-WIRE,SPEAKER WHITE WALL Accessories Description SBBSPRL BACK BOX,WALL,SPEAKER, RED SBBSPWL BACK BOX,WALL,SPEAKER,WHITE SBBCRL BACK BOX,CEILING,SPEAKER,RED SBBCWL BACK BOX,CEILING,SPEAKER,WHITE TR-2 TRIM RING,WALL, RED TR-2W TRIM RING,WALL,WHITE TRC-2 TRIM RING,CEILING,RED TRC-2W TRIM RING,CEILING,WHITE LED Lenses Description LENS-A3 Lens LED Amber Wall/Ceiling LENS-B3 Lens LED Blue Wall/Ceiling LENS-G3 Lens LED Green Wall/Ceiling LENS-R3 Lens LED Red Wall/Ceiling Bezels Description BZSPR WALL RED BEZEL KIT BZSPW WALL WHITE BEZEL KIT BZSPRC CEILING RED BEZEL KIT BZSPWC CEILING WHITE BEZEL KIT Notes for Bezels: tEach bezel pack ships in a package of 5. Add one of the following extensions for print/language options:-F(FIRE),-AL(ALERT),-EV(EVAC),-AG(AGENT),-P(Plain),-FR(FEU),-PG(FOGO),-SP(FUEGO), -SPE(FUEGO/FIRE) Bezels for use only with Speaker Strobes 3825 Ohio Avenue•St.Charles, IL 60174 USA System Sensor®is a registered trademark Phone:800-SENSOR2•Fax:630-377-6495 of Honeywell International,Inc. ^ www.systemsensor.com 1 �/�� ©2024 System Sensor. ST/Gr/ 3333 Unity Drive, Mississauga,ON L5L 3S6 Canada Product specifications subject to change without notice.Visit systemsensor.com �V SENSOR* Phone:800-SENSOR2•Fax:905 812 0771 for current product information,including the latest version of this data sheet. AVDS$2174:A•08/29/2024 www.systemsensor.ca 125 Pg.38 *, Th_ SYSTEM SENSOR® 1�1�1�1�1�1 ;,;1;1;1;1;1;1;1;- L Series Outdoor ''°'''°'''''''''''''''' . I.I.I.I1111.1.1.I.1.I.1 I.I.IIIIIIEI1.1.1.11111 Illlllll111/11llllllllll Speakers and '.'.'.'.'.'''.'.'.'.'.' 11111111111 Illllllllllllllllllll L-Series with LED �1'''';';:'',;;I:- Outdoor Speaker Strobes --- System Sensor L-Series and L-Series with LED audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Features The System Sensor L-Series Outdoor Speakers and • LED technology provides lower current draw L-Series with LED Outdoor Speaker Strobes offer the most • Weatherproof per NEMA 4X, IP56 as a standalone device versatile and easy-to-use line of weatherproof speakers and speaker • Rated from-40°F to 151°F strobes that can meet virtually any application requirement, including • Electrically compatible with legacy SpectrAlert,SpectrAlert indoor, outdoor, wet, dry, and washdown environment applications Advance and[-series devices at 16-33 VDC in temperatures from —40°F to 151°F. The speakers provide a broad • Field selectable candela settings on wall units: 15,30,75,95, frequency response range, low harmonic distortion offering a high- 110, 135,and 185 fidelity sound output while offering a high-volume sound output for use • Field-selectable candela settings on ceiling units: 15,30,75, in high ambient noise applications. 95, 115, 150,and 177 The L-Series Outdoor and [-Series with LED Outdoor appliances • Rotary switches for candela,speaker voltage(25 and 70.7 are NEMA 4X and IP56 rated without having to seal the back box. Vrms)and power settings(1/4,1/2, 1,and 2 watts) Additional caulk or sealant are not required on the back box for a faster, • Mounting plates with wirenuts are provided to make the cleaner installation. The L-Series platform offers a modern aesthetic connection between the field wiring and the mounting plates across the indoor and outdoor platform and design variations across • Synchronization through use of UL approved power supplies applications: wall or ceiling mount, red or white color choices, LED that support System Sensor Sync protocol or System Sensor colored lenses for distinctive visual signaling. In addition, installers MDL Sync Module can easily adjust appliances through rotary switches for candela, • Tamper-resistant construction speaker voltage and power settings. • Speakers and Speaker strobes listed for wall or ceiling use LED technology offers significantly lower current draw compared to • Speakers offer high fidelity and high volume sound output older Xenon bulbs across a full candela range.This improves design flexibility for notification appliance circuits(NACs)while also reducing power supply requirements allowing for simpler and lower cost installations. UL listed waterproof wirenuts are provided to make the connection between the field wiring and the mounting plates. Agency Listings The outdoor devices ship with plastic back boxes that accommodate in-and-out wiring for daisy chaining devices. Knock-outs located on SIGNALING SIGNALING ® €+�— r, the back eliminate the need to drill holes for screw-in mounting. C UL US C UL uS (O LISTED LISTED APPROVED 11 Note: When replacing SpectrAlert Advance products, the backbox Speaker-Strobes: Speakers: 3057383 7125-1653:0538 must be updated to the[-Series with LED backbox. S4048 S4048 3057493 7125-1653:0539 p AVDS-62185-00•03/17/2025•Page 1 126 Pg.39 Product Specifications Physical/Electrical Specifications Standard Operating Temperature -40°F to 151 °F(-40°C to 66°C)) Humidity Range 0 to 95±5% Power 1/4,1/2, 1,2 Watts Frequency Range 400 to 4000 Hz Maximum Supervisory Voltage(Speakers) 50 VDC Maximum Supervisory Voltage(Strobe) 33 VDC Strobe Flash Rate 1 Flash Per Second Nominal Voltages,Speakers 25 Volts or 70.7 Volts(nominal) Nominal Voltage,Strobe Regulated 24 VDC Operating Voltage Range,Strobe 16 to 33 VDC Input Terminal Wire Gauge 12 to 18 AWG Dimensions Wall Speaker Strobes(including lens) 6.69" L x 5.16" W x 2.47" D (170mm L x 131mm W x 63mm D) Wall Speaker Strobes(including lens)with SBBSPRUWL Surface 6.69" L x 5.16" W x 4.72" D (170mm L x 131mm W x 120mm D) Mount Back Box Ceiling Speaker Strobes(including lens) 6.97"diameter x 2.23"D(177mm x 57mm) Ceiling Speaker Strobes(including lens)with SBBCRUWL Surface 6.97"diameter x 4.73"D(177mm x 127mm) Mount Back Box Wall Speakers 6.69"L x 5.16"W x 1.72"D(170mm L x 131mm W x 44mm D) Wall Speakers with SBBSPRUWL Surface Mount Back Box 6.69"L x 5.16"W x 3.97"D(1700mm L x 131mm W x 101mm D) Ceiling Speakers 6.97"diameter x 1.2"D(177mm x 31mm) Ceiling Speakers with SBBCRUWL Surface Mount Back Box 6.97"L diameter x 3.97"D(177mm x 101mm) NOTE:SBBSPRL/WL Surface Mount Back Box intended for speaker strobes and speakers. Minimum Speaker Strobe Sound Output 1/aW 1/zW 1 W 2W UL Reverberant(dBA @10 ft) 77 81 83 85 UL Anechoic(dBA @10 ft) 77 81 83 85 Minimum Speaker Only Sound Output 1/aW 1/zW 1 W 2W UL Reverberant(dBA @10 ft) 77 81 83 85 UL Anechoic(dBA @10 ft) 77 81 83 85 UL/ULC Current Draw UUULC Maxmimum Strobe Current Draw(mA) Candela 16-33 Volts Rating Wall Ceiling Candela 15 18 18 Range 30 22 22 75 70 70 95 75 75 110 85 — 115 — 90 135 105 — 150 — 110 177 — 115 185 120 — AVDSE2185-00•03/17/2025•Page 2 127 Pg.40 L-Series Dimensions 3.971 - [100,86] �� ' 4.128 2.250 �[57,15] -L m�` o o °�°�70 I-/���1 �� -1°1' '0 0°o 0 0`®'�',°n �/,� rCOa0000 ,,,, („ or j 'l �� Dot®00000000Do000000l° o 'l / �e 0®A�oO°ooD00380oo0or, o �I� 0®r,DO°o0°000°000°o00,1a0 b ®mr,0°D°0®D°0°o00°000,1om A �� { DroDo°0000010 0 0 ®ro°°00o°°r6 � � s.701 0®+,0°°0°0°0°0°0°o°oo,a®0 0 ��i c [170,221 °°a,.o°0Do00°o°0000000re°° o r� oorr0®0°oDo°°Do00ooe°+'o° �o I, 1 ��_ 0°1,0000 RODI9°0°0°°,18° ro .7 �/ 00�,0000000 0,o0oDODo,�Om i ,1,p0a° 000},1,, 0 r 1°r°1 �1° O o° r1 '1w1r 1r °,°1°'0'Hr 1�1�1 1�1 ri Outdoor Wall Speaker with Surface Mount Back Box(SBBSPRU SBBSPWL) 3.965 [100,71] 1076.97 2.300 \� [176,97] [63,5] __ *8 " �o�o oda O�d4 S . 0 y' {1�' ®l�� 000 tat / 01.1114 I t j%�'OOp0��0$og og pip Op��Od 1�110�00051 °8°O°•o 9959,0p�0db0 I ® .� � DUUUO°°o o° D°0°DO�U�� M. i o pop°oaaa °°o o=°°a° �oaao pop 0 8 l 137•'�r �� w ;„I p�o� poaoo®� ° poop Opp ���� ��Y�I(411_ - - ire �Qpp���� �O000®evo�o°o�po�00®0 '� 1���' I��' tx o�pg�Aoo 0 o °n°op0 0 ' i0y "; Outdoor Ceiling Speaker with Surface Mount Back Box (SBBCRUSBBCWL) 4.722 [119,95] 250 Q4.131 -1'114114 4.128 [104,93]2[57,15] / � �r \ . ) ® °°:0; oo o:a-7-'7,N _ li I c -t� � b l 7) .40 tre [170,15] °�'1;1pi°,1.1°,°inDo oDpi 01 q W� - ,11 l ;� ��� my ___ ___ (t. F<` Outdoor Wall Speaker Strobes with Surface Mount Back Box(SBBSPRUSBBSPWL) AVDS-62185-00•03/17/2025•Page 3 128 Pg.41 4.987 [126,68] 4.394 [111,62] 06C 969 2.500 ® - [63,5] Iii a 0, 44iiiiirlrtiAV ‘thlielire Outdoor Ceiling Speaker Strobes with Surface Mount Back Box(SBBCRL/SBBCWL) L-Series with LED: Ordering Information Model Description L-Series with LED Outdoor Speaker Strobes SPSRKLED Outdoor Speaker Strobe,Wall, Red SPSRKLED-P Outdoor Speaker Strobe,Wall, Red, Plain SPSRKLED-B Outdoor Speaker Strobe,Wall, Red, Bilingual SPSWKLED Outdoor Speaker Strobe,Wall,White SPSWKLED-P Outdoor Speaker Strobe,Wall,White,Plain SPSWKLED-B Outdoor Speaker Strobe,Wall,White,Bilingual SPSWKLED-CLR-ALERT Outdoor Speaker Strobe,Wall,White,Alert,Clear lens SPSCWKLED Outdoor Speaker Strobe,Ceiling,White SPSCWKLED-P Outdoor Speaker Strobe,Ceiling,White,Plain SPSCWKLED-B Outdoor Speaker Strobe,Ceiling,White,Bilingual SPSCWKLED-CLR-ALRT Outdoor Speaker Strobe,Ceiling,White,Alert,Clear lens L-Series Outdoor Speakers SPRKL Outdoor Speaker,Wall,Red,Plain SPWKL Outdoor Speaker,Wall,White, Plain SPCWKL Outdoor Speaker,Ceiling,White, Plain Accessories SBBSPRL Back Box,Wall,Speaker,Red SBBSPWL Back Box,Wall,Speaker,White SBBCRL Back Box,Ceiling,Speaker,Red SBBCWL Back Box,Ceiling,Speaker,White LED Lenses LENS-A3 Lens LED Amber Wall/Ceiling LENS-B3 Lens LED Blue Wall/Ceiling LENS-G3 Lens LED Green Wall/Ceiling LENS-R3 Lens LED Red Wall/Ceiling Notes for L-Series with LED Outdoor Speaker Strobes: • All-P models have a plain housing(no"FIRE"marking on cover.) • All-ALERT models have"ALERT"marking on cover. • All-B models have"FIRE/FEU"marking on cover. 3825 Ohio Avenue•St.Charles, IL 60174 USA Phone:800-SENSOR2•Fax:630-377-6495 System Sensor®is a registered trademark www.systemsensor.com of Honeywell International,Inc. V 3333 Unity Drive, Mississauga,ON L5L 3S6 Canada ISTEM Phone:800-SENSOR2•Fax:905-812-0771 ©2025 System Sensor . Product specifications subject to change without notice.Visit systemsensor com �� SEAISOR• www.systemsensor.ca for current product information,including the latest version of this data sheet. AVDS-62185-00•03/17/2025 129 Pg.42 9 cg$ ig d N O C0686 VM`ewi)IeA 116 0°§ ij _ > , 'env uo;6uiyseM'M 00£Z ,N o E g E sepea6d� leU!W e±�iy ewpjeA ii: ) m b� 2 g g g Es ` d n o 1 ag LL e mi J * 4\ \\V A �\A V A A ... . ..-A y \ \ `\ \ \ \ \ \ \ ®� �\ � \� t ` v , v of\ ix 4 o dli gar 1 1 I o 0 _ _ u s ‘, , l' q -, , : d _ 7 � §G g \l / 130